Bryant 580D Product Information Manual

Commercial single package rooftop gas heating/electric cooling units 3 to 25 tons

Advertisement

COMMERCIAL
SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNITS
580D036-072
580D090-150
Standard-Efficiency Rooftop Units with:
• Exclusive integrated gas control board with diagnostics
• Alumagard™ heat exchanger coating
• Induced-draft fan for gas combustion
• Tubular, dimpled heat exchangers
• Pre-painted galvanized steel cabinet for long life and quality
appearance
• Commercial strength baserails with built-in rigging capability
• Convertible design for horizontal supply/return
• Non-corrosive, sloped condensate drain pan, meets ASHRAE
62-89 (IAQ)
• Two-inch return-air filters
• A wide assortment of factory-installed options available, in-
cluding high static drives that provide additional performance
range
FEATURES/BENEFITS
Every compact one-piece unit arrives fully assembled, charged,
tested, and ready to run.
579F180,216
579F240,300
INTEGRATED GAS UNIT CONTROLLER (IGC) (All Models)
— All ignition components are contained in the compact IGC
which is easily accessible for servicing. The IGC control board,
designed and manufactured exclusively for Bryant rooftop units,
provides built-in diagnostic capability. An LED (light-emitting di-
ode) simplifies troubleshooting by providing visual fault notifica-
tion and system status confirmation.
The IGC also contains an exclusive anti-cycle protection for gas
heat operation. After 4 continuous cycles on the unit high-
temperature limit switch, the gas heat operation is disabled, and
an error code is issued. This feature greatly improves reliability
of the rooftop unit.
Form No. PDS 580D.36.8
Model 579F/580D
Sizes 036-300
3 to 25 Tons

Advertisement

Table of Contents
loading

Summary of Contents for Bryant 580D

  • Page 1 — All ignition components are contained in the compact IGC which is easily accessible for servicing. The IGC control board, designed and manufactured exclusively for Bryant rooftop units, provides built-in diagnostic capability. An LED (light-emitting di- ode) simplifies troubleshooting by providing visual fault notifica- tion and system status confirmation.
  • Page 2 LP (liquid propane) conversion kit is available, if required. SAFETY IS BUILT IN — All 580D and 579F units have a flame rectification sensor to quickly sense the burner flame and ignite burners almost immediately. Fast shutdown is a certainty since the sensor reacts quickly to any flame outage or system failure.
  • Page 3: Table Of Contents

    flow during Stage 1 (unloaded) operation. All other 579F/ 580D units have the exclusive Acutrol™ metering device which precisely controls refrigerant flow, preventing slugging and flood-back, while maintaining optimum unit performance.
  • Page 4 MODEL NUMBER NOMENCLATURE 580D036-150 MODELS ONLY *Contains high pressure, (loss-of-charge) low-pressure, and freeze protec- tion cutout switches. NOTE: The example model number 580DEV090180CB designates a 7 ⁄ ton 460-3-60 volt gas/electric rooftop unit with 180,000 Btuh natural gas heat, Durablade economizer, and alternate drive.
  • Page 5 MODEL NUMBER NOMENCLATURE (cont) 579F180-300 MODELS ONLY NOTE: The example model number 579FEV180230CB designates a 15-ton 460-3-60 volt gas/electric rooftop unit with 230,000 Btuh natural gas heat input, economizer, and the standard low-medium fan drive static capability.
  • Page 6 NOMINAL STANDARD UNIT 580D TONS NOMINAL UNIT TONS 580D072 580D090 ⁄ 580D102 ⁄ 580D120 580D150 ⁄ 579F180 579F216 579F240 579F300 LEGEND Bels — Sound Levels (1 bel = 10 decibels) — Dry Bulb — Energy Efficiency Ratio IPLV — Integrated Part-Load Values SEER —...
  • Page 7 HEATING CAPACITIES AND EFFICIENCIES — 580D036-150 HEATING INPUT UNIT 580D (Btuh) Stage 2/Stage 1 036 074 —/ 72,000 036 115 115,000/ 82,000 048 074 —/ 72,000 048 115 —/115,000 048 150 150,000/120,000 060 074 —/ 72,000 060 115 —/115,000 060 150...
  • Page 8 UNIT SIZE 580D NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Al/Cu* Cu/Cu* Economizer Durablade Parablade Roof Curb† COMPRESSOR Quantity No. Cylinders (per Circuit) Oil (oz) REFRIGERANT TYPE Expansion Device Operating Charge (lb-oz) Circuit 1 Circuit 2 CONDENSER COIL Rows...Fins/in.
  • Page 9 UNIT SIZE 580D FURNACE SECTION Rollout Switch Cutout Temp (F)** Burner Orifice Diameter (in..drill size) Natural Gas Liquid Propane Pilot Orifice Diameter (Quantity) in..drill size Natural Gas Liquid Propane Thermostat Heat Anticipator Setting (amps) 208/230 v and 575 v Stage 1...
  • Page 10 UNIT SIZE 580D NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Al/Cu* Cu/Cu* Economizer Durablade Parablade Roof Curb† COMPRESSOR Quantity No. Cylinders (per Circuit) Oil (oz) REFRIGERANT TYPE Expansion Device Operating Charge (lb-oz) Circuit 1 Circuit 2 CONDENSER COIL Rows...Fins/in.
  • Page 11 UNIT SIZE 580D FURNACE SECTION Rollout Switch Cutout Temp (F)†† Burner Orifice Diameter (in..drill size) Natural Gas Liquid Propane Pilot Orifice Diameter (Quantity) in..drill size Natural Gas Liquid Propane Thermostat Heat Anticipator Setting (amps) 208/230 v and 575 v Stage 1...
  • Page 12 UNIT SIZE 579F NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Economizer Roof Curb† COMPRESSOR Model No..Quantity (Number of Cylinders) Oil (oz) No. of Cylinders (per circuit) Cooling Capacity Stages (%) REFRIGERANT TYPE Expansion Device Operating Charge (lb-oz) Circuit 1** Circuit 2 CONDENSER COIL Rows...Fins/in.
  • Page 13 UNIT SIZE 579F FURNACE SECTION Rollout Switch Cutout Temp (F)†† Burner Orifice Diameter (in..drill size) Natural Gas Thermostat Heat Anticipator Setting (amps) 208/230 v Stage 1 Stage 2 460 v Stage 1 Stage 2 Gas Input (Btuh) Stage 1 Stage 2 Efficiency (Steady State) (%) Temperature Rise Range...
  • Page 14 †Field-installed. ††Not available with horizontal adapter curb (180-300). NOTES: 1. Refer to 579F/580D price pages or contact your local representative for accessory and option package information. 2. For units being installed in California Air Quality Management Districts which require emissions of 40 nanograms/joule or less, kit CRLOWNOX001A00 must be in- stalled (sizes 036-060).
  • Page 15 Like the base unit, the economizer is converted easily for horizontal discharge applications. OPTIONS AND ACCESSORIES (cont) Designed specifically for use with Bryant commercial sys- tems, this Bryant programmable thermostat features LED occupied/unoccupied displays and setback mode which can override continuous fan operation.
  • Page 16 ACCUSENSOR™ II CONTROL (036-150 Only) ACCUSENSOR III Accusensor economizer controls help provide efficient, economical economizer operation. Accusensor II solid-state enthalpy control in- cludes the logic and one sensor to calculate both dry- and wet-bulb of the outdoor air to provide an accurate enthalpy reading on 036-150 units.
  • Page 17 Bottom of unit to combustible surfaces (when not using curb), 1 inch. Bottom of base rail to combustible surfaces (when not using curb) 0 inches. BASE UNIT DIMENSIONS — 580D036-072 UNIT 580D Weights are for unit only (aluminum plate fins) and do not include options or crating. CONNECTION SIZES ⁄...
  • Page 18 CORNER WEIGHT* UNIT 580D *Weights are for units only (aluminum plate fins) and do not include options or crating. BASE UNIT DIMENSIONS — 580D090-150 DIMENSIONS ‘‘H’’ ‘‘J’’ ‘‘K’’ ft-in. ft-in. ft-in. ⁄ ⁄ 1050 ⁄ ⁄ 1013 ⁄ 1050 ⁄...
  • Page 19 BASE UNIT DIMENSIONS — 579F180,216 DIMENSIONS UNIT 579F ft-in. ft-in. 1219 1090 CORNER WEIGHT* UNIT 579F *Weights are for unit only (aluminum plate fins) and do not in- clude options or crating. NOTES: 1. Dimensions in ( ) are in millimeters. Center of gravity.
  • Page 20 BASE UNIT DIMENSIONS — 579F240,300 NOTES: 1. Dimensions in ( ) are in millimeters. Center of gravity. Direction of airflow. 4. Ductwork to be attached to accessory roof curb or adapter only. 5. Minimum clearance: a. Rear: 7 0 (2134) for coil removal. This dimension can be reduced to 4 0 (1219) if conditions permit coil removal from the top.
  • Page 21 ROOF CURB UNIT SIZE ‘‘A’’ ACCESSORY 580D CRRFCURB001A00 1 -2 [356] 036-072 CRRFCURB002A00 2 -0 [610] ACCESSORY DIMENSIONS ‘‘D’’ ALT UNIT SIZE ‘‘B’’ ‘‘C’’ DRAIN 580D HOLE ⁄ 1 -9 ⁄ 1 -4 036-072 ⁄ [45] [551] [406] ⁄ *Either connector package available for either roof curb.
  • Page 22 UNIT ROOF CURB ‘‘A’’ SIZE ACCESSORY 580D 1 -2 CRRFCURB003A00 [356] 090- 2 -0 CRRFCURB004A00 [610] ACCESSORY DIMENSIONS (cont) UNIT ‘‘D’’ ALT ‘‘E’’ SIZE ‘‘B’’ ‘‘C’’ DRAIN 580D HOLE ⁄ 090- 2 -8 ⁄ 1 -10 ⁄ ⁄ [827] [583] [45] ⁄...
  • Page 23 NOTES: 1. Roof curb accessory is shipped unassembled. 2. Insulated panels, 1 thick neoprene coated, 1 3. Dimensions in ( ) are in millimeters. Direction of airflow. 5. Roof curb: 16 ga. (VA03-56) steel. CURB PKG. NO. REF. DESCRIPTION HEIGHT 1 -2 Standard curb 308450-201...
  • Page 24 ACCESSORY DIMENSIONS (cont) Horizontal Supply/Return Adapter Installation 2'-1 5/8" 2'-2 1/16" NOTE: 389210-201 is a fully factory preassembled horizontal adapter and includes an insulated high static regain transition duct which substantially improves fan static performance. The Barometric Relief Damper and Power Exhaust accesso- ries are not available with the horizontal adapter.
  • Page 25: Selection Procedure

    SELECTION PROCEDURE (with 579F180 example) I DETERMINE COOLING AND HEATING REQUIRE- MENTS AT DESIGN CONDITIONS. Given: Required Cooling Capacity ... . 170,000 Btuh Sensible Heat Capacity ....114,000 Btuh Required Heating Capacity .
  • Page 26: Performance Data

    580D036 (3 TONS) Air Entering Evaporator — Cfm/BF Temp (F) 900/0.11 1200/0.14 Air Entering Condenser Air Entering Evaporator — Ewb (F) (Edb) 42.8 38.9 35.0 44.8 40.8 37.0 45.8 41.9 38.2 20.0 24.5 28.7 21.8 27.5 32.8 23.0 30.0 36.0 2.91 2.81 2.70 2.99 2.88 2.78 3.02 2.92 2.82 40.8 36.9 33.3 42.5 38.7 35.0 43.6 39.9 36.1 19.4 23.7 27.9 21.0 26.8 31.8 22.6 29.7 35.1...
  • Page 27 580D090 (7 ⁄ TONS) Air Entering Evaporator — Cfm/BF Temp (F) 2250/0.07 2800/0.09 Air Entering Condenser Air Entering Evaporator — Ewb (F) (Edb) 102.8 94.8 86.2 105.8 98.2 90.0 106.4 99.0 90.8 109.2 101.6 93.6 49.4 61.8 73.2 52.6 67.8 81.6 7.14 6.82 6.50 7.28 6.98 6.68 98.2 90.2 81.6 101.8 93.6 85.2 102.6 94.4 86.0 104.6...
  • Page 28 580D120 (10 TONS) Air Entering Evaporator — Cfm/BF Temp (F) 3000/0.095 Air Entering Condenser Air Entering Evaporator — Ewb (F) (Edb) 135.8 124.8 112.0 66.8 82.6 97.4 9.76 9.41 9.10 130.0 119.6 104.0 64.3 80.5 93.8 10.41 10.07 9.74 124.1 113.7 96.7 62.2...
  • Page 29 579F180 (15 TONS) Temp (F) 4500/0.08 Air Entering Condenser (Edb) 212.0 195.0 179.0 101.0 126.0 148.0 15.20 14.70 14.20 205.0 188.0 171.0 98.5 123.0 145.0 16.60 16.10 15.50 197.0 180.0 162.0 95.8 120.0 141.0 18.00 17.40 16.70 190.0 172.0 152.0 93.3 117.0 136.0...
  • Page 30 579F240 (20 TONS) Temp (F) 6000/0.06 Air Entering Condenser (Edb) 274.0 250.0 226.0 130.4 163.6 194.4 16.92 16.40 15.90 264.0 240.0 216.0 127.6 159.8 189.8 18.54 18.00 17.36 252.0 228.0 204.0 124.4 155.4 184.6 20.20 19.52 18.82 240.0 216.0 190.6 120.0 150.8 178.4...
  • Page 31 FAN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS 580D036 (3 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 V (Cfm) Watts 0.49 0.21 1000 0.42 0.23 1100 0.37 0.24 1200 0.33 0.26 1300 0.27 0.27 1400 0.20 0.29 1500 0.16 0.30 LEGEND...
  • Page 32 FAN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont) 580D048 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 V (Cfm) Watts 1200 0.68 0.41 1300 0.61 0.42 1400 0.53 0.45 1500 0.45 0.47 1600 0.36 0.49 1700 0.26 0.52 1800 0.15...
  • Page 33 FAN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont) 580D060 (5 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 V 230, 460, 575 V (Cfm) Watts 1500 0.69 0.67 1.01 0.71 1600 0.49 0.70 0.85 0.74 1700 0.29 0.73 0.70 0.77 1800...
  • Page 34 FAN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont) 580D072 (6 TONS)* Airflow (Cfm) Watts 1800 0.70 0.66 1900 0.80 1023 0.78 2000 1022 0.91 1068 0.90 2100 1063 0.99 1115 1.00 2200 1104 1.13 1039 1159 1.15 2300 1130 1.26 1156 1202 1.29...
  • Page 35 FAN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont) 580D090 (7 ⁄ TONS)* Airflow (Cfm) Watts 2250 0.55 2300 0.57 2400 0.63 2500 0.69 2550 0.72 2600 0.75 2700 0.83 2800 0.90 2900 0.98 3000 1.07 3100 1.16 1047 3200 1.26 1131 3300 1.36...
  • Page 36 FAN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont) 580D102 (8 ⁄ TONS)* Airflow (Cfm) Watts 2550 0.72 2600 0.75 2700 0.83 2800 0.90 2900 0.98 3000 1.07 3100 1.16 1047 3200 1.26 1131 3300 1.36 1216 3400 1.47 1310 3500 1.59 1413 3600...
  • Page 37 FAN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont) 580D120 (10 TONS)* Airflow (Cfm) Watts 3000 0.76 3100 0.83 3200 0.90 3300 0.98 3400 1.06 3500 1.15 1039 3600 1.24 1114 3700 1.33 1190 3800 1.43 1275 3900 1.54 1370 4000 1.64 1456 4100...
  • Page 38 FAN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont) 580D150 (12 ⁄ TONS)* Airflow (Cfm) Watts 3750 1.41 1300 1.64 3800 1.46 1340 1.69 3900 1.56 1423 1.80 4000 1.67 1514 1.92 4100 1.79 1615 2.05 4200 1.91 1717 2.18 4300 2.04 1828 2.32...
  • Page 39 FAN PERFORMANCE — 580D036-150 HORIZONTAL DISCHARGE UNITS 580D036 (3 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 v (Cfm) Watts 0.54 0.21 1000 0.49 0.23 1100 0.43 0.24 1200 0.39 0.26 1300 0.33 0.27 1400 0.26 0.29 1500 0.21 0.30 LEGEND...
  • Page 40 FAN PERFORMANCE — 580D036-150 HORIZONTAL DISCHARGE UNITS (cont) 580D048 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 v (Cfm) Watts 1200 0.75 0.41 1300 0.68 0.42 1400 0.60 0.45 1500 0.51 0.47 1600 0.42 0.49 1700 0.32 0.52 1800 0.21...
  • Page 41 FAN PERFORMANCE — 580D036-150 HORIZONTAL DISCHARGE UNITS (cont) 580D060 (5 TONS) — STANDARD MOTOR (DIRECT DRIVE) Low Speed Airflow 208 V 230, 460, 575 V (Cfm) Watts 1500 0.74 0.67 1.06 0.71 1600 0.54 0.70 0.90 0.74 1700 0.34 0.73 0.75 0.77 1800...
  • Page 42 FAN PERFORMANCE — 580D036-150 HORIZONTAL DISCHARGE UNITS (cont) 580D072 (6 TONS)* Airflow (Cfm) Watts 1800 0.63 0.73 1900 0.73 0.83 2000 0.84 1022 0.94 2100 1015 0.97 1063 1.10 2200 1060 1.10 1104 1.20 2300 1104 1.25 1123 1130 1.27 2400 1138 1.30...
  • Page 43 FAN PERFORMANCE — 580D036-150 HORIZONTAL DISCHARGE UNITS (cont) 580D090 (7 ⁄ TONS)* Airflow (Cfm) Watts 2250 0.53 2300 0.55 2400 0.60 2500 0.66 2550 0.69 2600 0.72 2700 0.79 2800 0.86 2900 0.94 3000 1.02 3100 1.11 1006 3200 1.21 1089 3300 1.31...
  • Page 44 FAN PERFORMANCE — 580D036-150 HORIZONTAL DISCHARGE UNITS (cont) 580D102 (8 ⁄ TONS)* Airflow (Cfm) Watts 2550 0.69 0.94 2600 0.72 0.97 2700 0.79 1.05 2800 0.86 1.13 2900 0.94 1.21 3000 1.02 1.30 3100 1.11 1006 1.39 3200 1.21 1089 1.49 3300 1.31...
  • Page 45 FAN PERFORMANCE — 580D036-150 HORIZONTAL DISCHARGE UNITS (cont) 580D120 (10 TONS)* Airflow (Cfm) Watts 3000 0.68 3100 0.74 3200 0.81 3300 0.88 3400 0.96 3500 1.04 3600 1.13 1022 3700 1.23 1106 3800 1.33 1190 3900 1.44 1284 4000 1.55 1378 4100 1.67...
  • Page 46 FAN PERFORMANCE — 580D036-150 HORIZONTAL DISCHARGE UNITS (cont) 580D150 (12 ⁄ TONS)* Airflow (Cfm) Watts 3750 1.24 1162 1.48 3800 1.28 1194 1.52 3900 1.37 1267 1.62 4000 1.47 1349 1.71 4100 1.56 1423 1.82 4200 1.66 1506 1.92 4300 1.77 1598 2.04...
  • Page 47 579F180 (15 TONS) Airflow (Cfm) Watts 4500 1.05 4800 1.25 1110 5100 1.47 1306 5400 1.71 1519 1008 5700 1.98 1758 1049 6000 1016 2.28 2025 1091 6300 1059 2.60 2309 1133 6600 1104 2.96 2629 1174 6900 1150 3.35 2975 1218 7200...
  • Page 48 FAN PERFORMANCE — 579F180-300 UNITS (cont) 579F216 (18 TONS)* Airflow (Cfm) Watts 5000 1.10 1019 1.40 5500 1.40 1292 1.80 6000 1.80 1617 2.20 6500 2.20 1992 2.60 7000 2.70 2427 3.10 7200 2.94 2624 3.34 7500 3.30 2919 3.70 8000 3.90 3476...
  • Page 49 FAN PERFORMANCE — 579F180-300 UNITS (cont) 579F240 (20 TONS)* Airflow (Cfm) Watts 6000 1.80 1617 6500 2.20 1992 7000 2.70 2427 7500 3.30 2919 8000 3.90 3476 1047 8500 1026 4.60 4102 1097 9000 1079 5.40 4800 1147 9500 1133 6.20 5576 1199...
  • Page 50 FAN PERFORMANCE — 579F180-300 UNITS (cont) 579F300 (25 TONS)* Airflow (Cfm) Watts Rpm 7,500 3.39 3123 1039 3.81 8,000 1017 4.04 3717 1091 4.48 8,500 1072 4.76 4385 1143 5.23 9,000 1128 5.57 5129 1196 6.07 9,500 1185 6.47 5955 1250 6.99 10,000 1241...
  • Page 51 579F180-300 HORIZONTAL SUPPLY/RETURN FAN PERFORMANCE NOTES: 1. Dimensions are in millimeters. 2. The 389210-201 high static regain adapter accesso- ries may be used to provide horizontal supply/return. UNIT MINIMUM CFM 580D036 580D048 1200 580D060 1500 580D072 1800 580D090 2250 580D102 2550 SOUND A-WEIGHTED...
  • Page 52 ACCESSORY/FIOP STATIC PRESSURE* (in. wg) − 580D036-072 COMPONENT Durablade Economizer 0.05 Parablade Economizer 0.08 LEGEND FIOP − Factory-Installed Option *The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts.
  • Page 53 Durablade Economizer Barometric Relief Damper Characteristics — 580D036-150 Parablade Economizer Barometric Relief Damper Characteristics — 580D036-072 PERFORMANCE DATA (cont) Parablade Economizer Barometric Relief Damper Characteristics — ALTITUDE COMPENSATION* — ELEVATION (ft) 0-2,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000...
  • Page 54 ALTITUDE COMPENSATION* — 580D090-150 125,000, 180,000, AND 224,000 BTUH NOMINAL INPUT ELEVATION Natural Liquid (ft) Propane Orifice Orifice Size† Size† 0-2,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 *As the height above sea level increases, there is less oxygen per cubic foot of air.
  • Page 55 EVAPORATOR-FAN UNIT MOTOR Standard 580D036 Alternate Standard 580D048 Alternate Standard 580D060 Alternate 580D072 Standard 580D090 Standard 580D102 Standard Standard 580D120 Alternate Standard 580D150 Alternate 579F180 Standard 579F216 Standard 579F240 Standard 579F300 Standard LEGEND Bhp — Brake Horsepower *Extensive motor and electrical testing on these units ensures that the full horsepower range of the motors can be utilized with confidence.
  • Page 56: Electrical Data

    VOLTAGE NOMINAL UNIT VOLTAGE 580D TYPE (60 Hz) 208/230 (single phase) 208/230 (3 phase) (3 Tons) (3 phase) (3 phase) 208/230 (single phase) 208/230 (3 phase) (4 Tons) (3 phase) (3 phase) 208/230 (single phase) 208/230 (3 phase) (5 Tons)
  • Page 57 COMPRESSOR VOLTAGE NOMINAL RANGE NO. 1 UNIT VOLTAGE (60 Hz) 208/230 61.0 (3 phase) Tons) 28.0 (3 phase) 208/230 35.6 (3 phase) Tons) 17.8 (3 phase) 208/230 35.6 (3 phase) Tons) 17.8 (3 phase) 208/230 43.6 (3 phase) Tons) 22.1 (3 phase) LEGEND —...
  • Page 58: Typical Piping And Wiring

    TYPICAL PIPING AND WIRING — 580D036-150 Vertical Discharge Ducting NEC — National Electrical Code Horizontal Discharge Ducting...
  • Page 59 TYPICAL PIPING AND WIRING — 579F180-300 (579F180 shown) NEC — National Electrical Code...
  • Page 60: Typical Wiring Schematics

    TYPICAL WIRING SCHEMATIC — 580D036-150 NOTES FOR 580D036-150 UNITS: 1. If any of the original wire furnished must be re- placed, it must be replaced with Type 90 C wire or its equivalent. 2. Three-phase motors are protected under pri- mary single phasing conditions.
  • Page 61 TYPICAL WIRING SCHEMATIC (579F240-300, 460-v shown)
  • Page 62 TYPICAL WIRING SCHEMATIC (579F240-300, 460-v shown) (cont) — Adjustable Heat Anticipator BKR W/AT — Breaks with Amp Turns — Burner Relay — Contactor, Compressor — Capacitor — Circuit Breaker — Cooling Compensator — Crankcase Heater — Compressor Lockout COMP — Compressor Motor —...
  • Page 63: Controls

    OPERATING SEQUENCE Cooling, Units Without Economizer — When thermostat calls for cooling, terminals G and Y1 are energized. The indoor (evaporator) fan contactor (IFC) and compressor contactor no. 1 (C1) are energized, and evaporator-fan motor (IFM), com- pressor no. 1 (580D036-150 and 579F216-300) or unloaded compressor (579F180), and condenser fan(s) start.
  • Page 64 Cooling, Units With Parablade Economizer (580D036-072) — When the outdoor air is above the enthalpy control (EC) set- ting, and the room thermostat calls for cooling, and the com- pressor contactor is energized to start the compressor and the condenser-fan motor. The evaporator-fan motor is energized and the economizer damper moves to the minimum position.
  • Page 65: Application Data

    1. DUCTWORK (580D036-150) — Secure vertical discharge ductwork to roof curb. For horizontal discharge applica- tions, attach ductwork to unit, or field-supplied flanges can be attached to horizontal discharge openings and all duct- work attached to flanges. 2. DUCTWORK (579F180-300) — Ductwork should be at- tached to the curb on all units.
  • Page 66 NOTE: Do not drill in this area, damage to basepan may result in water leak. Concentric Duct Air Distribution 579F180-300 Only APPLICATION DATA (cont) NOTE: Dimensions A, A and B, B are obtained from field-supplied ceiling diffuser. indicates block-off panels. Concentric Duct Details 579F180-300 Only...
  • Page 67 G. Unit shall be designed in accordance with ISO 9001, and shall be manufactured in a facility registered to ISO 9002/ BS5750, Part 2. H. Each 580D unit is subjected to completely automated run testing on the assembly line. Each unit contains a factory- supplied printout indicating tested pressures, amperages, data, and inspectors;...
  • Page 68 GUIDE SPECIFICATIONS — 580D036-150 (cont) 5. The integrated gas controller (IGC) board shall include gas heat operation fault notification using an LED (light-emitting diode). 6. Unit shall be equipped with anti-cycle protection with one short cycle on unit flame rollout switch or 4 con- tinuous short cycles on the high-temperature limit switch.
  • Page 69 b. Damper shall close upon indoor (evaporator) fan shutoff. c. Designed to close damper during loss of power situations. d. Equipped with 15% barometric relief damper. 5. 25% Two-Position Damper: a. Two-position damper package shall include single blade damper and motor. Admits up to 25% out- door air.
  • Page 70 PACKAGED ROOFTOP ELECTRIC COOLING UNIT WITH GAS HEAT — CONSTANT VOLUME APPLICATION HVAC GUIDE SPECIFICATIONS SIZE RANGE: 15 TO 25 TONS, NOMINAL (COOLING) 172,000 to 360,000 BTUH, NOMINAL (INPUT HEATING) MODEL NUMBER: 579F Part 1 — General 1.01 SYSTEM DESCRIPTION Unit is an outdoor rooftop mounted, electrically controlled heating and cooling unit utilizing a reciprocating semi- hermetic compressor(s) for cooling duty and gas combus-...
  • Page 71 H. Filter Section: Standard filter section shall consist of 2 sizes of factory- installed 2-in. thick throwaway fiberglass filters of commercially available sizes. I. Controls and Safeties: 1. Unit Controls: a. Economizer control (optional) b. Capacity control (2-step) c. Unit shall be complete with self-contained low- voltage control circuit.
  • Page 72 12. Commercial Programmable Thermostat: Seven-day commercial progammable thermostat shall be capable of auto-changeover, F/C, 3-stage Copyright 1998 Bryant Heating & Cooling Systems GUIDE SPECIFICATIONS — 579F180-300 heating and 2-stage cooling. Thermostat shall also be equipped with complete system status display.