Electrical Data — Unit 589A - Bryant 588A Installation, Start-Up And Service Instructions Manual

Single package gas heating/ electric cooling units
Hide thumbs Also See for 588A:
Table of Contents

Advertisement

VOLTAGE
UNIT
RANGE
SIZE
V-PH-Hz
589A
Min
024
208/230-1-60
187
030
208/230-1-60
187
208/230-1-60
187
036
208/230-3-60
187
460-3-60
414
208/230-1-60
187
042
208/230-3-60
187
460-3-60
414
208/230-1-60
187
048
208/230-3-60
187
460-3-60
414
208/230-1-60
187
060
208/230-3-60
187
LEGEND
AWG
— American Wire Gage
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and
Refrigeration
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
RLA
— Rated Load Amps
*Fuse or HACR Breaker.
† Carrier Scroll Compressor.
**Copeland Scroll Compressor.
NOTES:
1. In compliance with NEC (National Electrical Code) requirements for
multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the unit
shall be fuse or HACR breaker. The CGA (Canadian Gas Associa-
tion) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table, deter-
mine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent-
age of voltage imbalance.
% Voltage imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Table 4B — Electrical Data — Unit 589A
OUTDOOR-FAN
COMPRESSOR
Max
RLA
LRA
253
12.9
62.5
253
15.0
76.0
253
16.7
95.0
253
10.9
75.0
506
5.4
40.0
253
20.0
104.0
253
13.9
88.0
506
6.8
44.0
253
26.4
129.0
253
15.0
99.0
506
8.2
49.5
253
32.1
169.0
253
19.3
123.0
INDOOR-FAN
MOTOR
MOTOR
FLA
FLA
1.4
2.0
1.4
2.6
1.4
2.8
1.4
2.8
0.8
1.4
1.4
3.1
1.4
3.1
0.8
1.6
1.4
7.2
1.4
7.2
0.8
2.3
2.1
7.2
2.1
7.2
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.
IMPORTANT:
If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
—20—
AWG 60 C
POWER SUPPLY
MIN WIRE
SIZE
MCA
MOCP*
19.5
30
12
22.8
30
10
25.1
30
10
17.8
25
12
9.0
10
14
29.5
45
10
21.9
30
10
10.9
15
14
41.6
60
6
27.4
40
10
13.4
20
14
49.4
60
6
33.4
50
8
AB = 452 v
BC = 464 v
AC = 455 v
452
464
Average Voltage =
3
1371
=
3
= 457
7
457
= 1.53%
MAX WIRE
LENGTH (ft)
75
100
95
70
100
80
60
100
100
70
100
100
90
455

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

589a