Output Module
Output Module – C078
Galaxy Output Modules can be added to the Galaxy 3 Series control panels. Each additional Output Module
expands the system up to 16 outputs by simulating the outputs of four RIO's
The following figure shows the main components of the Output Module.
Secondary Output
Connectors (RM1-4)
for Relay Module
Normally Open
relay output
Jumper
Tamper switch
and spring

Addressing

The Galaxy Output Module must be given a unique address before it is connected to a power supply. This
base address is selected using the Rotary Address Switch. Valid addresses are shown in the following table.
NOTE: The zones represented by the Output Module addresses can be viewed on the panel, however they
are not used.
Galaxy Panel
Primary Outputs
+
-
12 11 10 9
CN3
DIP
Switch
RM3
BUZZER
ext
int
RM1
MODE TEST
CN1
-
+
1 2 3 4
Configuration
Primary Outputs
Jumpers
Figure 3.3. Galaxy Output Module
No of Output Modules
(Maximum)
3-48
8 (line 1)
3-144
8 (line 2)
15 (line 1)
3-520
16 (lines 2-4)
Table 3-9. Valid Output Module Addresses
Galaxy 3 Series Installation Manual
Connector for
Primary Outputs
firmware upgrade
+
16 15 14 13
RM4
ISP
LED
Rotary
Address
Switch
RM2
TAMPER
Bypass
+
5 6 7 8
Primary Outputs
Valid Addresses
4
1-8 (line 1)
0-7 (line 2)
1-9, A-F (line 1)
0-9, A-F (lines 2, 3, 4)
3-8
-
CN4
}
B
RS485 line
A
B
-
(0V)
A
-
+
+
(12V)
-
(0V)
Engineer
+
(12V)
Socket
(RS485 line)
S (screen cable
connect)
CN2
-
2, 3, 4, 5
}
Module
power
supply