Zone Addressing with Onboard RIO Switch

The RIO switch (SW3, dipswitch 8) controls the ordering of the on-board RIO's. This dipswitch must be set
before powering up the panel.
NOTE: The RIO switch is not functional on the 3-48. It defaults to the Switch off configuration.
Switch off (default)
When the switch is set to this mode, the onboard RIO's configure to the following addresses:
Onboard RIO0
Onboard RIO1
Switch on
When the switch is set to this mode, the onboard RIO's configure to the following addresses:
Onboard RIO0
Onboard RIO1
PANEL
3-48
3-144
3-520

Wiring Zones

The zones on Galaxy 3 Series panels can be Double Balanced (default) or End of Line. Zones can be pro-
grammed with different resistance ranges for zone status activation (see Galaxy 3 Series Programming
Manual, IP1-0033, parameter 51.46 = Parameters.Zone Resistance). Refer to Table 2-8 (Double
Balanced) or Table 2-9 (End of Line) for details of the zone resistance and resulting conditions.
NOTE: The circuit debounce time (the period the zone must remain in a state to register a change in condi-
tion) is 300 milliseconds by default.
Preset 1 - 1k
Tamper S/C
0 - 800
Low Res
800 - 900
Normal
900 - 1200
High Res
1200 - 1300
Open
1300 - 12000
Masked
12000 - 15000
Tamper O/C
15000 - infinity
Table 2-8. Double Balanced Zone
Resistance and Conditions
Zone address range:
Zone address range:
Zone address range:
Zone address range:
ON-BOARD RIO RANGE
1001 - 1008, 1011 - 1018
1001 - 1008, 1011 - 1018,
0011 - 0018 (switch on)
1001 - 1008, 1011 - 1018,
0011 - 0018 (switch on)
Table 2-7. Zone Address Ranges
Preset 2 - 2k2
Preset 3 - 4k7
0 - 1800
0 - 3700
1800 - 2000
3700 - 4200
2000 - 2500
4200 - 5500
2500 - 2700
5500 - 6500
2700 - 12000
6500 - 19000
12000 - 15000
19000 - 22000
15000 - infinity
22000 - infinity
Galaxy 3 Series Installation Manual
1001-1008
Outputs:
1011-1018
Outputs:
1001-1008
Outputs:
0011-0018
Outputs:
TOTAL
RIO's
16
Line 1 (4)
16
Line 1 (8)
Line 2 (8)
16
Line 1 (15)
Line 2 (16)
Line 3 (16)
Line 4 (16)
Preset 1 - 1k
Tamper S/C
0 - 800
Low Res
800 - 900
Normal
900 - 1200
High Res
1200 - 1300
Masked
1300 - 12000
Open
12000 - infinity
Table 2-9. End of Line Zone Resistance
and Conditions
2-14
1001-1004
1011-1014
1011-1014
0011-0014
TOTAL
48
144
520
Preset 2 - 2k2
Preset 3 - 4k7
0 - 1800
0 - 3700
1800 - 2000
3700 - 4200
2000 - 2500
4200 - 5500
2500 - 2700
5500 - 6500
2700 - 12000
6500 - 19000
12000 - infinity
19000 - infinity