Solenoid coil of the electronic refrigerant
control valve (ERCV) ............ Indoor unit
Measure the resistance between No. 5 (GRY lead wire) and other terminals (another color of
lead wires) of 5P (WHT) plug connected to the solenoid coil.
Refer to "1-2-(A) Major component specifications".
8
Compressor motor (CM) ......... Outdoor unit
In case of single -phase compressor
Remove the cover of compressor terminal and measure the resistance
between terminals.
Refer to "1-2 Major component specifications".
9
Compressor motor magnetic contactor (52C) ............ Outdoor unit
Measure the resistance between A (ORG lead wire) and B (GRY lead wire) terminals on
the compressor motor magnetic contactor.
Refer to "1-3 Other component specifications".
Check the continuity between contactors.
MODEL
Push button on
the magnetic
contactor
no press
press
0
Solenoid coil of 4-way valve (20S) ... Outdoor unit
Measure the resistance between No.1 (BLK lead wire) and No.2 (BLK lead wire) terminals
of 2P (BLK) socket connected to the solenoid coil.
Refer "1-3 Other component specifications".
FMCA–1UL
Pair of terminals
R – U
S – V
T – W
––––
––––
––––
YES
YES
YES
– 91 –
4. Service procedures
*Measure the coil resistance.
*Measure the coil resistance.
31 – 32
YES
––––
*Measure the coil resistance.
Section
1
2
3
4
SM830076