Sanyo XHS3632 Service Manual page 9

Split system air conditioner
Hide thumbs Also See for XHS3632:
Table of Contents

Advertisement

1-1 Unit Specifications
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity*
Moisture removal (High)
Air circulation (Hi)
S.E.E.R. (H.S.P.F.)
ELECTRICAL RATINGS
Voltage rating
Available voltage range
Running amperes
Max. running amperes
Power input*
Buck-up heater
Maximum fuse size
FEATURES
Controls
Fan speeds Indoor / Outdoor
Timer
Air deflection
Air filter
Operation sound
Hi / Me / Lo
Refrigerant control
REFRIGERANT PIPING
Limit of piping length
Limit of piping length at shipment
Limit of elevation difference
between the two units
Refrigerant piping
Flare type
Indoor Unit
Outdoor Unit
BTU / h
(17 F)**
Pints / h
cu.ft. / min.
BTU / Wh
VAC
VAC
A
A
W
(17 F)**
kW
A
Horizontal / Vertical
Indoor
dB - A
Outdoor - Hi
dB - A
ft.
(m)
ft.
(m)
ft.
(m)
Narrow pipe
in. (mm)
Wide pipe
in. (mm)
– 9 –
XHS3632
CH3632
230 - 208 VAC / 1 Phase / 60 Hz
Cooling
34,500
33,500
11.1
11.1
980 / 880
10.7
11.0
230
208
187 - 253
15.4
15.8
3,350
3,200
30
Microprocessor
3 and Automatic control / 2 (Auto)
ON / OFF 24-hours & Program
— / Automatic
Washable, easy access, long life fiter (2,500 hr)
43 / 40 / 36
56
Electronic Refrigerant Control Valve
165 (50)
100 (30)
Outdoor unit is higher than indoor unit: 165 (50)
Outdoor unit is lower than indoor unit: 100 (30)
3 / 8 (9.52)
3 / 4 (19.05)
1. Specifications
Heating
37,500
36,500
25,000
23,500
(7.0)
(7.0)
230
208
187 - 253
18.2
19.3
3,850
3,750
3,150
2,950
SM830076
1
2
3
4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ch2432Xhs2432Ch3632

Table of Contents