Meanings Of Alarm Messages - Sanyo XHS3632 Service Manual

Split system air conditioner
Hide thumbs Also See for XHS3632:
Table of Contents

Advertisement

(3)

Meanings of alarm messages

If an error occurred in the air conditioner, the error condition is presented by indicating the
error code in the wired remote controller display or by the combination of lamp statuses for
operation, timer and heat stand-by (OFF status and flashing status).
Possible causes of troubles
Remote controller is detecting
unusual signal from indoor unit.
• Indoor unit is detecting unusual signal from the remote controller and group control.
(No serial communications signal)
Section
Improper setting of indoor unit or
1
remote controller.
Indoor unit is detecting unusual
signal from signal option.
Improper setting of indoor unit or
remote controller.
Indoor unit is detecting unusual
signal from outdoor unit.
2
Outdoor unit is detecting
unusual signal from indoor unit.
Auto. address setting is not
correct.
Indoor unit is detecting unusual
signal from another indoor unit.
3
Improper setting of indoor unit or
remote controller.
4
Improper wiring connections of ceiling panel.
Protective device in indoor unit
is activated.
Protective device in outdoor unit
is activated.
Error receiving of serial communications signal.
Error transmitting of serial communications signal.
Indoor unit address setting is duplicated.
Remote controller address (RCU.ADR) is duplicated.
Error transmitting of serial communications signal
Error receiving of serial communications signal.
When using flexible combination control, main indoor unit address
setting is duplicated. (judged by outdoor unit.)
Error receiving of serial communications signal.
Error transmitting of serial communications signal
Error receiving of serial communications signal.
(Confirmation error of unit numbers included)
Error transmitting of serial communications signal.
No. of judged indoor units or total capacity of indoor units is small.
No. of judged indoor units or total capacity of indoor units is large.
Error transmitting of serial communications signal
Error receiving of serial communications signal.
Indoor unit group address is not correct.
Model setting of indoor unit is not matching the outdoor unit.
When using group control, main indoor unit address setting is duplicated.
(judged by indoor unit.)
Outdoor unit address is duplicated.
Improper wiring between indoor units.
(There is a group connection wiring in case of individual control.)
Indoor unit address (or group address) is not set.
Capacity code of indoor unit is not set.
Improper wiring of group control wiring.
Indoor unit model setting is improper (capacity)
Thermal protector in indoor fan motor is activated.
Float switch is activated.
• Thermal protector in outdoor fan motor is activated.
• Compressor thermal protector is activated.
• Power supply voltage is unusual. (The voltage is more than
260 V or less than 160 V.)
Discharge gas temperature of comp. is unusual.
High pressure switch is activated.
Voltage drops.
Other indooor unit is warning.
– 58 –
4. Service procedures
Wired remote
Wireless remote
controller
controller
display
display
E01
Operation lamp
flashes
E02
O: Operation lamp
E03
: Timer lamp
E08
:Heat stand-by
lamp
E09
E10
E11
E14
E04
Heat stand-by
lamp flashes
E05
E06
:Operation lamp
: Timer lamp
O: Heat stand-by
E07
lamp
E15
E16
E17
E18
L01
Operation lamp and
heat stand-by lamp
L02
flash at the same time.
L03
O: Operation lamp
: Timer lamp
L04
O: Heat stand-by
L07
lamp
L08
L09
L11
L13
: Operation lamp
P09
O: Timer lamp
P01
O: Heat stand-by
lamp
P10
Operation lamp and heat
P02
stand-by lamp flash
alternately.
O: Operation lamp
: Timer lamp
P03
O: Heat stand-by
P04
lamp
P05
P31
SM830076