Trane CGAM Installation & Operation Manual page 88

Air-cooled scroll chillers 20 - 130tons
Hide thumbs Also See for CGAM:
Table of Contents

Advertisement

Installation - Electrical
Table 48.
All Object Types Sorted by Object Name (
(a)
Object Identifier
Object Name
Analog Input, 64
Phase CA Voltage- Compressor 1B
Analog Input, 65
Phase AB Voltage- Compressor 2A
Analog Input, 66
Phase BC Voltage- Compressor 2A
Analog Input, 67
Phase CA Voltage- Compressor 2A
Analog Input, 68
Phase AB Voltage- Compressor 2B
Analog Input, 69
Phase BC Voltage- Compressor 2B
Analog Input, 70
Phase CA Voltage- Compressor 2B
Analog Input, 71
Line 1 Current (in Amps)- Compressor 1A
Analog Input, 72
Line 2 Current (in Amps)- Compressor 1A
Analog Input, 73
Line 3 Current (in Amps)- Compressor 1A
Analog Input, 74
Line 1 Current (in Amps)- Compressor 1B
Analog Input, 75
Line 2 Current (in Amps)- Compressor 1B
Analog Input, 76
Line 3 Current (in Amps)- Compressor 1B
Analog Input, 77
Line 1 Current (in Amps)- Compressor 2A
Analog Input, 78
Line 2 Current (in Amps)- Compressor 2A
Analog Input, 79
Line 3 Current (in Amps)- Compressor 2A
Analog Input, 80
Line 1 Current (in Amps)- Compressor 2B
Analog Input, 81
Line 2 Current (in Amps)- Compressor 2B
Analog Input, 82
Line 3 Current (in Amps)- Compressor 2B
Analog Input, 83
Line 1 Current (%RLA)- Compressor 1A
Analog Input, 84
Line 2 Current (%RLA)- Compressor 1A
Analog Input, 85
Line 3 Current (%RLA)- Compressor 1A
Analog Input, 86
Line 1 Current (%RLA)- Compressor 1B
Analog Input, 87
Line 2 Current (%RLA)- Compressor 1B
Analog Input, 88
Line 3 Current (%RLA)- Compressor 1B
Analog Input, 89
Line 1 Current (%RLA)- Compressor 2A
Analog Input, 90
Line 2 Current (%RLA)- Compressor 2A
Analog Input, 91
Line 3 Current (%RLA)- Compressor 2A
Analog Input, 92
Line 1 Current (%RLA)- Compressor 2B
Analog Input, 93
Line 2 Current (%RLA)- Compressor 2B
Analog Input, 94
Line 3 Current (%RLA)- Compressor 2B
Analog Input, 95
Number of Circuits
Analog Input, 96
Number of Compressors, Ckt 1
Analog Input, 97
Number of Compressors, Ckt 2
Multi-State Input, 1
Running Mode
Multi-State Input, 2
Operating Mode
Multi-State Input, 3
MP Communication Status
Multi-State Input, 4
Refrigerant Type
Multi-State Input, 5
Model Information
Multi-State Input, 6
Cooling Type
Multi-State Input, 7
Manufacturing Location
Binary Output, 1
Chiller Auto Stop Command
Binary Output, 2
Remote Diagnostic Reset Command
Binary Output, 4
Noise Reduction Request
Binary Output, 1
Chiller Auto Stop Command
88
Refer to previous tables for detailed descriptions of objects
Description
Phase CA voltage, compressor 1B.
Phase AB voltage, compressor 2A.
Phase BC voltage, compressor 2A.
Phase CA voltage, compressor 2A.
Phase AB voltage, compressor 2B.
Phase BC voltage, compressor 2B.
Phase CA voltage, compressor 2B
Line 1 Current (in Amps)- Compressor 1A
Line 2 Current (in Amps)- Compressor 1A
Line 3 Current (in Amps)- Compressor 1A
Line 1 Current (in Amps)- Compressor 1B
Line 2 Current (in Amps)- Compressor 1B
Line 3 Current (in Amps)- Compressor 1B
Line 1 Current (in Amps)- Compressor 2A
Line 2 Current (in Amps)- Compressor 2A
Line 3 Current (in Amps)- Compressor 2A
Line 1 Current (in Amps)- Compressor 2B
Line 2 Current (in Amps)- Compressor 2B
Line 3 Current (in Amps)- Compressor 2B
Line 1 Current (%RLA)- Compressor 1A
Line 2 Current (%RLA)- Compressor 1A
Line 3 Current (%RLA)- Compressor 1A
Line 1 Current (%RLA)- Compressor 1B
Line 2 Current (%RLA)- Compressor 1B
Line 3 Current (%RLA)- Compressor 1B
Line 1 Current (%RLA)- Compressor 2A
Line 2 Current (%RLA)- Compressor 2A
Line 3 Current (%RLA)- Compressor 2A
Line 1 Current (%RLA)- Compressor 2B
Line 2 Current (%RLA)- Compressor 2B
Line 3 Current (%RLA)- Compressor 2B
Number of Circuits
Number of Compressors, Ckt 1
Number of Compressors, Ckt 2
Indicates the primary running mode of the chiller.
Indicates the primary operating mode of the chiller.
Communication status.
Refrigerant type.
Indicates the model type of the chiller.
Cooling type of the condenser.
Location where chiller was manufactured.
Allows the chiller to run if conditions for running are met.
Resets remotely diagnostics that can be reset.
Requests chiller to enter mode to reduce noise.
Allows the chiller to run if conditions for running are met.
) (continued)
CG-SVX17E-EN

Hide quick links:

Advertisement

Table of Contents
loading