Trane CGAM Installation & Operation Manual page 149

Air-cooled scroll chillers 20 - 130tons
Hide thumbs Also See for CGAM:
Table of Contents

Advertisement

Diagnostics
Table 80.
Communication diagnostics (continued)
Comm Loss: Heating EXV
Comm Loss: Heating EXV
Comm: Heating EXV
Comm Loss: High Pressure Cutout Switch
Comm Loss: High Pressure Cutout Switch
Comm: High Press Cutout Sw
Comm Loss: Local BAS Interface
Comm Loss: Local BAS Interface
Comm: Local BAS Interface
Comm Loss: Night Noise Setback Relay
Comm Loss: Night Noise Setback Relay
Comm: Night Noise Setbk Rly
Comm Loss: Op Status Programmable Relays
Comm Loss: Op Status Programmable Relays
Comm: Op Status Relays
Comm Loss: Outdoor Air Temperature
Comm Loss: Outdoor Air Temperature
Comm: Outdoor Air Temp
Comm Loss: Percent Capacity Output
Comm Loss: Percent Capacity Output
Comm: Percent Capacity Out
Comm Loss: Phase Protection Fault Input
Comm Loss: Phase Protection Fault Input
Comm: Phase Protect Flt Inp
Comm Loss: Power Factor Correction Fault Input
Comm Loss: Power Factor Correction Fault
Comm: Pwr Fac Correction Flt
Comm Loss: Receiver Fill Valve Relay
Comm Loss: Receiver Fill Valve Relay
Comm: Receiver Fill Vlv Rly
Comm Loss: Reversing Valve
Comm Loss: Reversing Valve
Comm: Reversing Valve
Comm Loss: Subcooler Shutoff Valve Relay
Comm Loss: Subcooler Shutoff Valve Relay
Comm: Subcooler Shut Vlv Rly
Comm Loss: Suction Pressure Transducer
Comm Loss: Suction Pressure Transducer
Comm: Suction Pressure Xdcr
Comm Loss: Suction Temperature
Comm Loss: Suction Temperature
Comm: Suction Temperature
Comm Loss: Supplemental Heat Relay 1
Comm Loss: Supplemental Heat Relay 1
Comm: Supplmntl Heat Rly 1
Comm Loss: Supplemental Heat Relay 2
Comm Loss: Supplemental Heat Relay 2
Comm: Supplmntl Heat Rly 2
Comm Loss: Supplemental Heat Relay 3
Comm Loss: Supplemental Heat Relay 3
Comm: Supplmntl Heat Rly 3
Comm Loss: Supplemental Heat Relay 4
Comm Loss: Supplemental Heat Relay 4
Comm: Supplmntl Heat Rly 4
Excessive Loss of Comm
Excessive Loss of Comm
Excessive Loss of Comm
CG-SVX17E-EN
Circuit
Immediate Latch
All
Circuit
Immediate Latch
All
Warning
and
Non
Chiller
All
Special
Latch
Action
Chiller
Normal
Latch
All
Chiller
Warning
Latch
All
Chiller
Normal
Latch
All
Chiller
Warning
Latch
All
Chiller
Normal
Latch
All
Chiller
Warning
Latch
All
Circuit
Normal
Latch
All
Circuit
Normal
Latch
All
Circuit
Normal
Latch
All
Circuit
Immediate Latch
All
Circuit
Immediate Latch
All
Chiller
Warning
Latch
All
Chiller
Warning
Latch
All
Chiller
Warning
Latch
All
Chiller
Warning
Latch
All
Chiller
Immediate Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period. Use the last values sent from BAS.
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 sec period.
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 sec period.
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Continual loss of communication between the MP and
the Functional ID for relay 1 has occurred for a 35-40
second period.
Continual loss of communication between the MP and
the Functional ID for relay 2 has occurred for a 35-40
second period.
Continual loss of communication between the MP and
the Functional ID for relay 3 has occurred for a 35-40
second period.
Continual loss of communication between the MP and
the Functional ID for relay 4 has occurred for a 35-40
second period.
Loss of comm with 10 or more of the LLIDs configured
for the system has been detected. This diagnostic will
suppress the callout of all subsequent comm loss
diagnostics. Check power supply(s) and power
disconnects – troubleshoot LLID bus using TechView.
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
149

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents