Signal (Device) Explanations - Mitsubishi Electric Melservo-J3 Series MR-J3-B Instruction Manual

Melservo j3 series general-purpose ac servo sscnet compatible
Hide thumbs Also See for Melservo-J3 Series MR-J3-B:
Table of Contents

Advertisement

3. SIGNALS AND WIRING

3.5 Signal (device) explanations

For the I/O interfaces (symbols in I/O division column in the table), refer to section 3.7.2.
In the control mode field of the table
The pin No.s in the connector pin No. column are those in the initial status.
(1) Connector applications
Connector
CN1A
Connector for bus cable
from preceding axis.
CN1B
Connector for bus cable to
CN2
Encoder connector
CN4
Battery connection
CN5
Communication connector
(2) I/O device
(a) Input device
Device
Symbol
Forced stop
EM1
DI1
DI2
DI3
Name
Used for connection with the controller or preceding-axis servo amplifier.
Used for connection with the next-axis servo amplifier or for connection of the cap.
next axis
Used for connection with the servo motor encoder.
When using as absolute position detection system, connect to battery (MR-
connector
J3BAT).
Before installing a battery, turn off the main circuit power while keeping the control
circuit power on. Wait for 15 minutes or more (20 minutes or for drive unit 30kW or
more) until the charge lamp turns off. Then, confirm that the voltage between P( )
and N( ) (L
and others. Otherwise, an electric shock may occur. In addition, always confirm
from the front of the servo amplifier whether the charge lamp is off or not. Replace
the battery with main circuit power OFF and with control circuit power ON.
Replacing the battery with the control circuit power OFF results in loosing absolute
position data.
The personal computer is connected.
Connector
Pin No.
CN3-20
Turn EM1 off (open between commons) to bring the motor to an forced
stop state, in which the base circuit is shut off and the dynamic brake is
operated.
Turn EM1 on (short between commons) in the forced stop state to reset
that state.
When parameter No.PA.04 is set to "
ON) can be set inside.
CN3-2
Devices can be assigned for DI1 DI2 DI3 with controller setting.
For devices that can be assigned, refer to the controller instruction
manual. The following devices can be assigned for Q172HCPU
CN3-12
Q173HCPU QD75MH.
DI1: upper stroke limit (FLS)
CN3-19
DI2: lower stroke limit (RLS)
DI3: near-point dog (DOG)
Function/Application
and L
for drive unit 30kW or more) is safe with a voltage tester
Function/Application
1
3 - 24
", automatically ON (always
I/O
division
DI-1
DI-1
DI-1
DI-1