1. System Configuration

1.8 Real-time data link system

TOSLINE-F10
TOSLINE-F10 is a high speed data transmission system suited for small points I/O
distribution system. By inserting the TOSLINE-F10 remote module (FR112M), the
T1-16S can work as a remote station of the TOSLINE-F10 network. On this network,
the T1-16S sends 1 word data to the master station and receives 1 word data from
the master station.
Topology
Transmission distance
(without repeater)
Transmission speed
Scan transmission
capacity
Scan cycle
Error checking
NOTE
Typical data link configuration
The figure below shows the typical data link configuration.
T1-16S
Operator interface units
32
T1-16S User's Manual
Item
Bus (terminated at both ends)
500 m max. (total)
750 kbps
512 points (32 words) max.
7 ms/32 words
CRC check
(1) Refer to the separate "T1 User's Manual
Module " for details of the TOSLINE-F10 remote card (FR112).
(2) Refer to the separate TOSLINE-F10 User's Manual for details of
overall TOSLINE-F10 system.
computer
(master)
TOSLINE-F10
T1-16S
T1-16S
TOSLINE-F10 system specifications
High speed mode
Master
T2E
T2E
RI/O
(remote)
Long distance mode
1 km max. (total)
250 kbps
12 ms/32 words