7. Instructions
<Transmitting>
When the instruction input is ON, one set of message which is stored in the source table (from
start character to the trailing code) is transmitted through the RS-485 port. The execution
status is stored in the status flag.
The instruction input must be kept ON until the transmitting operation is complete.
Example
Source designation
D0010
H00
D0011
00500
D0500 (CPU register)
When R0001 is ON, one set of message (ended by the trailing code) stored in the range of
D0500 to D0511 (12 words) is transmitted through the RS-485 port.
Execution status:
Note
The XFER instruction is not executed as error in the following cases. In these cases, the
instruction error flag (ERF = S051) is set to ON. If the ERF is set to ON once, it remains ON until
resetting to OFF by user program.
(1) The leading address for the RS-485 port designation is other than 0.
(2) Transfer size is out of the range of 1 to 256.
(3) Mode setting of the RS-485 port is not the free ASCII mode.
(4) This instruction is programmed in the sub-program #1.
244
T1-16S User's Manual
H04
D0012
D0013
H0000 ... Normal complete
H0001 ... During transmitting the message
H0002 ... Communication busy
H0003 ... During the reset operation
H0004 ... Send time-out (from start character to the trailing code)
H0005 ... Send message length error (no trailing code in the source table)
Baudrate
300, 600, 1200 bps
30 seconds
2400 bps
15 seconds
4800 bps
7 seconds
9600 bps
3 seconds
19200 bps
1.5 seconds
Transfer size
00012
Execution status
Time-out setting
Destination designation
D0015
H00
H30
D0016
00000
T1S RS-485 port
6F3B0253