8. Special I/O Functions

8.1 Special I/O function overview

The T1-16S supports the special I/O functions as listed below.
Function name
Variable input filter
constant
High
speed
counter
Interrupt input function Immediately activates the corresponding I/O interrupt
Analog setting
function
Pulse output function
PWM output function
256
T1-16S User's Manual
Input filter constant (ON/OFF delay time) can be set
by user program. The setting range is 0 to 15ms
(1ms units). Default value is 10ms. This function is
applied for X000 to X007 (8 points as a block).
Single phase
Counts the number of pulses of single phase pulse
up-counter
train. 2 channels of pulse input are available. The
countable pulse rate is up to 5KHz for each channel.
Channel 1
Channel 2
Single phase
Counts the number of pulses in a specified sampling
speed-
time. The sampling time setting is 10 to 1000ms
counter
(10ms units). 2 channels of pulse input are available.
The countable pulse rate is up to 5KHz for each
channel.
Channel 1
Channel 2
Quadrature
Counts the 2-phase pulses whose phases are shifted
bi-pulse
90 each other. Counts up when phase A precedes,
counter
and counts down when phase B precedes.
The countable pulse rate is up to 5KHz.
Phase A
Phase B
Reset
program when the interrupt input is changed from
OFF to ON (or ON to OFF). 2 points of interrupt input
are available.
X002
Interrupt 1 (I/O interrupt program #3)
X003
Interrupt 2 (I/O interrupt program #4)
The value of the analog setting adjuster is converted
into digital value (0 to 1000) and stored in the SW
register. 2 adjusters are provided on the T1-16S.
V0
SW30
V1
SW31
Variable frequency pulse train can be output. The
available pulse rate is 50 to 5000Hz (1Hz units).
Y020
CW or Pulse (PLS)
Y021
CCW or Direction (DIR)
Variable duty cycle pulse train can be output. The
available ON duty setting is 0 to 100% (1% units).
Y020
PWM output
Function summary
X000 count input, X002 reset input
X001 count input, X003 reset input
X000 count input
X001 count input
X000
X001
X002
6F3B0253
Remarks
SW16 setting
is necessary to
use this
function. (Note)
Only one
among these 4
functions can
be selected.
SW16 is used
to select the
function.
(Note)
No function
selection is
required.
Either one
between these
2 functions
can be used.
SW26 is used
to select the
function. (Note)