1.5.2

I/O modules

The T1-16S can connect up to eight I/O modules.
The following 10 types of the I/O modules are available.
For specification details of the I/O modules, refer to the separate manual "T1-16S
User's Manual
Type
DI116M
DO116M
DD116M
RO108M
AD121M
AD131M
DA121M
DA131M
TC111M
FR112M
Expantion connector
NOTE
(1) If more than 8 I/O modules are connected, T1-16S cannot operate normally.
(2) The TOSLINE-F10 remote station module (FR112M) must be connected at the
right end. Tow or more FR112Ms cannot be used together.
I/O Modules ".
Description
16 points input, 24Vdc – 5mA
16 points output, 24Vdc – 100mA
8 points input, 24Vdc - 5mA
+ 8 points output, 24Vdc – 100mA
8 points relay output, 24Vdc/240Vac - 1A
1 channel analog input, 0 to 5V / 0 to 20mA
1 channel analog input, 10V
1 channel analog output, 0 to 20mA
1 channel analog output, 10V
1 channel thermo-couple input
TOSLINE-F10 remote station,
1 word input + 1 word output
FR112M
1. System Configuration
Other I/O modules
Expantion connectors
Basic Hardware and Function
6F3B0253
Power supply
Supplied from the
basic unit (5 Vdc)
25