7. Instructions
JCS
Jump control set / reset
JCR
Expression
Input
[ JCS ]
[ JCR ]
Function
When the JCS input is ON, instructions between JCS and JCR are skipped (not executed). When
the JCS input is OFF, ordinary operation is performed.
Execution condition
JCS
input
OFF
Ordinary operation
ON
Skips until JCR
Operand
No operand is required.
Example
When X000 is ON, the rung 2 circuit is skipped, therefore Y021 is not changed its state
regardless of the X001 state. When X000 is OFF, Y021 is controlled by the X001 state.
Note
JCS and JCR must be used as a pair.
Nesting is not allowed.