7. Instructions
FUN 090
MPX
Expression
Input
[ A MPX (n) B
Function
When the input is ON, the data of the register which is designated by B in the table, size n starting
with A, is transferred to C.
Execution condition
Input
OFF
No execution
ON
Normal execution
Pointer over (no execution)
Operand
Name
X
A Start of table
n Table size
B Pointer
C Destination
Example
When R010 is ON, the register data which is designated by RW30 is read from the table
D0500 to D0509 (10 registers size), and stored in D0005.
If the data of RW30 is 7, D0507 data is transferred to D0005.
Source table
D0500
D0501
D0507
12345
D0508
D0509
Note
If the pointer data designates outside the table (10 or more in the above example), the transfer
is not executed and the output comes ON.
The table must be within the effective range of the register address.
176
T1-16S User's Manual
Multiplexer
C ]
Output
Operation
Device
Y
R
S
T.
C. XW YW RW SW T
Pointer
0
1
7
8
9
Output
OFF
OFF
ON
Register
C
D
Destination
D0005
12345
6F3B0253
Constant Index
I
J
K
1 - 64
0 - 63