Toshiba PROSEC T1-16S User Manual page 249

Programmable controller basic hardware and function
Hide thumbs Also See for PROSEC T1-16S:
Table of Contents

Advertisement

< Data exchange mode (Mode 0) >
When the instruction input comes ON with the operand B+1 is 0, the Data exchange mode
(mode 0) is selected. In this mode, the T1-16S sends the following commands to the Inverters
starting from #0 through the Inverter number specified by the operand B, and repeats.
#0 Frequency reference write (FA01)
#0 Operation command write (FA00)
#1 Frequency reference write (FA01)
#1 Operation command write (FA00)
:
#n Frequency reference write (FA01)
Scan
#n Operation command write (FA00)
#0 Operating frequency monitor (FD00)
#0 Output terminal status monitor (FE07)
#1 Operating frequency monitor (FD00)
#1 Output terminal status monitor (FE07)
:
#n Operating frequency monitor (FD00)
#n Output terminal status monitor (FE07)
The maximum Inverter number #n is specified by the operand B.
The scan execution status and the Inverter communication status are stored in the operand
B+2 to B+7.
The command data table is specified by the operand A and A+1.
When the instruction input is reset to OFF, the operation is stopped after receiving the
response from the Inverter currently communicating.
Example
Data table designation
D1000
4
D1001
2000
When the data for each operand are set as above, the following operation condition is specified.
RW200=5
The max Inverter number is 5. Therefore T1-16S scans from #0 through #5 Inverters.
D1000=4 & D1001=2000
Parameter & status
RW200
5
RW201
0 (mode 0)
RW202
Execution status
RW203
Comm error code
RW204
RW205
Inverter comms
RW206
status map
RW207
D2000 is specified as the data table starting address.
7. Instructions
RS-485 port
D1010
H0030 (fixed)
D1011
Basic Hardware and Function
6F3B0253
0 (fixed)
247