Toshiba PROSEC T1-16S User Manual page 294

Programmable controller basic hardware and function
Hide thumbs Also See for PROSEC T1-16S:
Table of Contents

Advertisement

10. Troubleshooting
Error message and related information
Event
Sys RAM check err
Error
address
Sys ROM BCC error
Illegal
BCC
System power off
System power on
Sub-r nesting err
Program
type -
block No.
WD timer error
Address 1 Address 2
292
T1-16S User's Manual
Info 1
Info 2
Info 3
Error data Test data
Address
Sub-r No.
in the
block
Special
Meaning and countermeasures
device
S004
In the power-up initialization, an error has
S011
detected by system RAM read/write
checking. (Error down and programming
tool cannot be connected)
Replace the unit if the error remains after
power OFF and ON again.
S004
BCC error has been detected in the system
S010
program in the ROM. (Error down and
programming tool cannot be connected)
Replace the unit if the error remains after
power OFF and ON again.
Power OFF (no error)
Power ON (no error)
The nesting of subroutines exceeds 3
levels.
(Error down)
Correct the program.
S004
The watchdog timer error has occurred.
S01F
(Error down)
If the error occurs frequently, replace the
unit.
6F3B0253