Clearances To Combustibles; Insert Leveling - Superior SDVI Installation And Operation Manual

Direct-vent dave lennox signature collection
Table of Contents

Advertisement

MINIMUM CLEARANCES TO COMBUSTIBLES
Minimum clearances include any projections such as shelves, window
sills, mantels, spacers/standoffs or surfaces to combustible construction
etc. above the appliance. Paint or lacquer used to finish the mantel
must be heat resistant in order to avoid discoloration.
The letters below, E through J, correspond to Figure 5 showing minimum
clearances required from the appliance to combustibles and the minimum
projection of the hearth extension.
E = 31-1/2" (800mm) from Top Facing to Bottom of Insert
F = 25-1/2" (648mm) from Center of Glass to Side Facing or Side
Wall
J = 39" (991mm) from 10.5" (267mm) Mantel to Bottom of Insert
HEARTH PROTECTION
G =
Minimum Hearth Protection from Front of Insert*
H =
Vertical Distance from Insert Bottom to Combustible Material.
G
13"(330mm)
H
0"(0mm)
Note: Hearth protection to be min. 3/8" (10mm) thick non-combustible
or equivalent, with a k factor of .84.

INSERT LEVELING

At each front and rear corner of the insert is an adjustable leg provided
to level the insert should the hearth of the fireplace be uneven. To adjust
the legs, loosen the two 5/32" allen head screws, move the leg to the
desired height, and then tighten the screws. Repeat these steps for each
adjusting leg.
10"(254mm)
0"(0mm)
2"(21mm)
4"(102mm)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Facing and Mantel Clearances
3"/76mm
1-1/2"
38mm
33-1/2"
851mm
31-1/2"
800mm
Figure 4
Clearances
MANTEL
Mantel
TRIM
Trim
E
G
Figure 5
3"/76mm
3"/76mm
Facing and
Mantel
Side View
39-1/2"
1003mm
36-1/2"
927mm
F
C L
H
Hearth / Floor Protection
J
9