then the 'new primary' IP Gateway must establish connection with the Terminal server. In this
configuration, several minutes may elapse before the IP Gateway's mode changes take effect.
3. Both IP Gateways are connected to the MOSCAD system over an IP network. Using this
configuration, the IP Gateway's mode change takes effect immediately for requests going from
the IP Gateway to the RTUs. The SCADA should initiate a communication to the RTU
through the 'new' primary IP Gateway in order for the RTU being able to send Bursts to it.

Site Configuration

The IP Gateway is configured for redundancy through the IP Gateway Toolbox Site
Configuration utility.
To set up the site configuration,
1. Run the Site Configuration utility from the IP Gateway Toolbox.
2. Click on the SCADA tab in the workspace bar.
3. Under General System settings, set the 'Startup mode' parameter for the primary
IP Gateway to 'Redundant GW1'.
4. Save the site configuration file and download it to the primary IP Gateway.
5. Under General System settings, set the 'Startup mode' parameter for the secondary
IP Gateway to 'Redundant GW2'.
6. Make sure that the Site ID of the secondary IP Gateway is identical to the Site ID of the
primary IP Gateway.
7. Save the site configuration file and download it to the secondary IP Gateway.
6-17
IP Gateway Redundancy