Occupancy Determination; Instructions - Carrier 50PG20-28 Controls, Start-Up, Operation, Service And Troubleshooting Instructions

Single package rooftop units with comfortlink tmcontrols and puron (r-410a) refrigerant
Table of Contents

Advertisement

Shut Down on IDF Failure (IDF..F)
This conli_ration
applies only ifa tan switch is installed and configured. A YES
value wilt enable diagnostic Alert T409 to shut down the unit
when incorrect tan status is sensed. A NO value will still
permit Alert T409 but will not cause unit shutdown. The
factory default value is YES.
Economizer Installed (ECEN)
This confimlration identi-
fies if an economizer is installed. A YES value enables
economizer operation. A NO value disables economizer opera-
tion. This point is repeated in the Economizer Conlimlration
men u ( (_onfiguratio n ---_E ( ON ---_E C E?€).
Fan Status Switch (FN.SW)
This conliguration identifies
if a fan status switch is installed, and what status (normally
open, normally closed) the input is when the indoor fan is OFF.
Filter Status Switch (FL.SW)
This conlimaration identifies
if a filter status switch is installed, and what status (normally
open, nonnalty closed) the input is when the filter is CLEAN.
Fire Shutdown Switch (FS.SW)
This conliguration identi-
fies if a tire shutdo,a_ switch is installed, and what status
(normally open, normally closed) the input is when the fire or
smoke alarm is OFF (no alarm).
Remote Occupancy Switch (RM.SW)
This configuration
identifies if a relnote occupancy switch is installed, and what
status (normally open, nonnatly closed) the input is when
UNOCCUPIED.
SAT Settling Time (SAI:13
This configuration sets a sup-
ply air temperature settling time before using the reading for
compressor staDng in some units with multiple circuits. See
Adaptive Thermostat Control (U.CTL = 2, ECTL = 0) and
Space Sensor Control (U.(TL = 3) within the Cooling opera-
tion section for more information. The factory default value is
240 seconds.
SAT Heat Mode Sensing (SAT.H)
This conlimlration con-
trols the display of the supply-air temperature during heating
operation. A DISABLE value wilt force the displayed supply-
air temperature (SAT) to zero when heat is ON and for 5 lnin-
utes after. A ENABLE value will display the temperature at all
tilnes. See the Heating sections for more intbnnation. The
factory delhult is DISABLE due to the factory SAT sensor
location. This point is repeated in the Heating Conligmration
menu.
RAT Sensor On SPTO Input (RAT.S)
This conliguration
identifies if a return air temperature (RAT) sensor is installed
on the space temperature oft;et (SPTO) input. A YES value
enables RAT display. A NO value disables RAT display.
RH Sensor On OAQ Input (RH.S)
This conlimaration
identifies if a space relative humidity sensor is installed on the
outdoor air quality (OAQ) input. A YES value enables SP.RH
display. Ifa Humdi-MiZer
TM
unit, then the unit determines de-
humidification demand based on this input and the appropriate
set point. A NO value disables SERH display and use.
Space Hmnidity Switch (RH.SW)
This
conlimaration
identifies if a space relative hmnidity switch is installed on the
ENTHALPY input, and what status (normally open, normally
closed) the input is when the space humidity is LOW.
Temperature Compensated Start Coolin_ Factor (TCS.C)
This factor is used in the equation of the Temperature Compen-
sated Start Time Bias for cooling. A setting of 0 minutes
indicates Temperature Compensated Start in Cooling is not
permitted.
Temperature Compensated Start Heating Factor (TCS.H)
This factor is used in the equation of the Temperature Compen-
sated Start Time Bias for heating. A setting of 0 minutes
indicates Temperature Compensated Start in Heating is not
permitted.
Occupancy
Determination--Many
factors deter-
mine whether the unit considers the building occupied or
unoccupied. If the unit is operating with a space temperature
sensor (T-55, T-56 or T-58), occupancy affects the unit set
points and the operation of the economizer. If the unit is
operating under thermostat control, occupancy only affects the
operation of the economizer. The factors affecting occupancy
are listed below fiom highest to lowest priority.
1. The CCN point OCCUPIED is forced via an extemat
device such as a ComfortID
TM
controller: When OCCU-
PIED is forced to YES, the unit is considered occupied.
When OCCUPIED is forced to NO, the unit is considered
unoccupied. If OCCUPIED is not being forced, proceed
to the level 2 priority.
2. Remote Occupancy Switch should be conlimared to either
Normally Open or Normally Closed when the user would
like to control the occupancy with an external switch.
This switch is field-supplied (24-v, single pole, single
throw [SPST]). There are three possible confimarations
for the remote occupancy switch: No Switch (0), Normal-
ly Open (1) or Nonnalty Closed (2). This confimlration is
accessible on the display at Cot*figuration--_UNIT--_
RM.SPK If the switch is conlim,lred to No Switch (0), the
switch input value will be ignored and software will
proceed to the level 3 priority. For each type of switch,
the appropriate confimlration and states are listed in the
table below.
SWITCH
TYPE OF SWITCH
CONFIGURATION
Normal Open (1)
Occupied when
closed or Unoccupied
when open
Occupied when
open or Unoccupied
when closed
Normal Close (2)
STATE OF
SWITCH AND STATE
OF OCCUPANCY
Open and Unoccupied
Closed and Occupied
Open and Occupied
Closed and Unoccupied
NOTE: To perform relnote occupancy, an Econolnizer Control
Board must be installed in the unit.
3. The tbltowing occupancy options are determined by the
state of Occupancy Schedule Number (Configmvttion--_
CCN---_CH..O---_CH..N)
and the Global
Schedule
Broadcast (Configuration _'C(W-->BROD -->B. G S).
a. SCH.N = 0: The unit is always considered occupied
and the pro m'mnmed schedule is ignored. This is the
factory default.
b. SCH.N = 1-64: Follow the local progrmrnned sched-
ule. Schedules 1 to 64 are local within the controller.
The 48/50PG unit can only store one local schedule
and therefore changing this number only changes the
title of the schedule table.
c. SCH.N
= 65-99: Follow the global pro_mrnned
schedule. If the 48/50PG unit is configured as a
Global
Schedule
broadcaster
(Configuration
_CCN--+BROD--+B.GS = YES), the unit will tbl-
low the unit's pro mmrnned schedule and broadcast
the schedule so that other devices pro mmrnned to fol-
low this schedule number can receive the schedule. If
the 48/50PG
unit
is not
programmed
as
a
Global
Schedule
broadcaster
(Configuration
_CCN--+BROD--+B.GS = NO), the unit will receive
its intbnnation fiom the unit programmed to broad-
cast this schedule nmnber.
While using a pro mmrnned schedule, occupancy can
be
temporarily
switched
fiom
unoccupied
to
occupied
by pressing
the override
button
for
approximately 3 seconds on a T-55, T-56, or T-58
device. Override will only occur if Configuration
_'(W---_qCH..O_OV.SP
is set to YES. The length
of the override period is determined by the setting of
Configuration _'CCN---_qCH. 0 _'0 VEX.
40