Indoor Fan -- The indoor thn is controlled by the indoor
tan relay output (Outputs--->FA?_i9--->IDF) o n the MBB (main
base board) control, wNch then operates the indoor tan contac-
tor. The indoor fan may operate during cooling with compres-
sors mode, fiee cooling with outdoor air mode, heating mode,
or for ventilation with outdoor air mode.
The indoor tan operation can be affected by configurations
for thermostat control type (Configuration---_UNIr---_T.CrL),
the occupancy thn configuration (Configuration---_UNIT---_
OC.FN),
the indoor air quality sensor tan configuration
(Configuration--+AIR.Q---_IA.F?€),
the indoor
air quality
switch tan configuration
((bnfiguration---_AIILQ---_ILF?€),
and the tan status switch configuration
((bnfiguration---_
UNIT--+ F?V:SW). For 48PG gas heating units without
Humidi-MiZer device, the IGC control tan output is also moni-
tored by the MBB control. This can result in additional modifi-
cation of fan delays or other operation due to safety functions
of the IGC control. See the Indoor Air Quality section if using
IAQ (indoor air quality) accessory sensors.
THERMOSTAT CONTROL
ha thermostat mode, the IDF
relay will be on in the following situations:
• If tan request G in ON, the IDF wilt be ON.
• If cooling request Y1 or Y2 is ON, the IDFwill
be ON.
• If heating request W1 or W2 is ON, the IDFwill
be ON.
SPACE SENSOR CONTROL
In Space Sensor Control
mode, the IDF (indoor tan) relay will be on in the following
situations. If the unit is in Occupied mode and the indoor fan is
configured to always run while occupied ((bnfiguration-->
UNIT _'OC.FN=
YES), the indoor l_aal wilt be ON. If OCFN
equals NO or the unit is unoccupied, the indoor tan will operate
only when heating or cooling is necessary.
Coo[in 0 -- Compressors will not operate if the outdoor
temperature is less than the value configured for the circuit
lockout
temperatures
((bnfiguration_DOL_'A.LO;
Configuration _'OOL
_B.LO;
and
Configuration
COOL _,CC.LO;). The Mthilnmn On Time (Configuration
(DOL ---_IR T.. O, and Minhnum Off Time (Configuration --+
COOL---_MOT.0 time guards apply to all compressors. Facto-
131default values are 3 minutes for Minilnum On Time and
5 minutes for Minilnuln OffTime.
If the indoor tan control is configured to cycle with the
cooling demand (Configumtion---_UNIT_OC.FN=
No),
the tan will stop after a configured delay (Configuration
_DOL---_FOD.C).
Factory default value is 60 seconds.
THERMOSTAT CONTROL
To operate the unit in The>
mostat
mode,
the
Unit
Control
Type
(Configuration
_UNIT--+U.(TL)
configuration must be set to 2 (Thermo-
stat). There are up to fore types of thermostat control depend-
ing on model size. These are configured with the Thermostat
Control Type (Configuration--+UNIT---_T.CTL).
For
economizer
equipped
units
(Configuration
_UNIT--+ECEN
= Yes), the Adaptive control atgorithln is
used whenever the economizer can provide cooling. TNs will
ensure proper time delays and SAT control when the econo-
mizer is cooling. Cooling
begins when the Y1 input is ener-
gized. The economizer
will try to provide cooling as described
in the Economizer
section. If the economizer
is not available
for cooling or the economizer
has been at 100% tbr 5 minutes,
compressor
staging will beNn.
Con[iguration---_UNIT---_T.CTL
= 0 (Adaptive)
When
T.(TL
= 0, additional
timers mad supply air temperature
limits
apply to control the compressor
staNng. In Adaptive
mode, a
stage of colnpression
wilt be turned off if the Supply-Air
Tem-
perature ( Temperatures
--+AIR. T---a7AI) is less than Minilnum
Supply Air Temperature
Lower Level (Setpoints--_AT.L).
In
addition, a stage of compression
will be turned on if the SATis
greater
than the Minhnum
Supply
Air Temperature
Upper
Level (Setpoin ts ---_qA T.U). If SA T.L and SAT. U are con figured
so that they axe close together,
the last stage of compressor
might cycle rapidly,
slowed
only by its minimum
on and
off-tilne
requirements.
Configurable
time delays
also apply
when
adding
stages
(Configuration_'COOL_.INO
or
removing
stages
(Configuration_DOL
_.DE
O.
C.INC
aald C.DEC
are accessible
via the Scrolling
Marquee
at
Configuration_'OOL.
Compressor
minilnmn
on-time
(Configuration
_,COOL ---_MRT.0 and compressor
minimmn
oil'-time (Configuration
_'OOL--_AIOT.
0 do apply.
T..CTL
1 (1 Stage Y1)
When
T.CTL
1, no additional
compressor
staging
timers
or supply
air temperature
limits
apply. Compressor
staging will follow the thermostat
inputs
directly. Y1 will turn on refrigerant
circuit A. Y2 will add re-
fiigerant
circuit B. Compressor
minimuln
on-tilne
(MRT. 0
mad compressor
minilnmn
off-time (MOT.O
do apply.
SPACE SENSOR
CONTROL
To
operate
the
unit
in
Space Sensor mode, set the Unit Control Type to 3 (Configum-
tion--+UNIT---_U.CTL=3).
To enable
heating
during
space
telnperamre
control, a jumper wire must be added bewveen R
mad W1 on the field connection
terminal strip (see Major Sys-
tem Components
section for wiring diagrams).
Because Space Sensor mode is ml "Auto" 1node, the control
will switch bewveen
cooling
and heating
to maintain
space
temperature.
However, to lninimize unnecessary
changes, there
is a 10-1ninute 1node select tilnegumd
(Operating
Modes---_
COOL---_MS. TG), after the last stage of heat rams off before
cooling is allowed.
The unit tries to maintain the space temperature
at the Occu-
pied Cool Set Point (Setpoints_O(SP)
or the Unoccupied
Coot
Set
Point
(Setpoints--+UCSP).
See
the
Occupancy
Determination
section for factors that affect the Occupied
sta-
res (Run Stams---_VIEW_OC
O. The Cooling Demmld (Op-
erating
Modes_DOL---A7PT---_DMD.
0
is equal to Space
Temperature
(Operating
Modes _'OOL
---AqPT---_qP1) minus
the occupied
or unoccupied
set point (DMD.C
SPY
set
point). See Table 37 for ml example of reading
and chmlging
the occupied set point (OCSP).
Table 37 -- Reading and Changing Cooling Occupied Set Point
DISPLAY
KEYPAD
ITEM
DISPLAY
ITEM EXPANSION
COMMENT
MENU
ENTRY
]
OCSP
78
Occupied CooI Set point
Default: 78
]
78
Scrolling Stops
]
78
Value flashes
SETPOINTS
]
Select 75
]
75
Change accepted
OCSP
75
Occupied CooI Set point