Carrier 50PG20-28 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 100

Single package rooftop units with comfortlink tmcontrols and puron (r-410a) refrigerant
Table of Contents

Advertisement

APPENDIX
A -- LOCAL
DISPLAY
AND CCN TABLES
(cont)
MODE -- CONFIGURATION
(cont)
ITEM
I
EXPANSION
CONFIGURATION
(cont)
AIR.Q
Air Quality Configuration
IA.CF
IAQ Analog
input Config
IA.FN
ILCF
ILFN
AQ.MN
EC.MN
OVR.P
OA.CF
OAQ.L
AQD.L
AQD.H
DF.ON
DF.OF
1.4M
1.20M
O.4M
O.20M
H,4M
H,2OM
ALM.O
A.SPC
A.SRT
A.OAT
A.CS
A.CMP
A.CKT
A.SSP
A.SCT
A.FAN
A.FIL
A.TST
A.ECO
TRIM
SPT.C
SPT.T
SAT.C
SAT.T
RAT.C
RAT.T
CCN
CCN.A
CCN.B
BAUD
BROD
B.TIM
B.OAT
B.GS
B.ACK
SCH.O
SCH.N
HOLG
OV.TL
OV.EX
OV.SP
LEGEND
IAQ Analog
Fan Config
IAQ Switch Input Config
IAQ Switch Fan Config
Econo Min IAQ Position
Econo Minimum
Position
IAQ Override Position
OAQ Analog
Input Cfg
OAQ Lockout
Limit
AQ Differential
Low
AQ Differential
High
Fan On AQ Differenfial
Fan Off AQ Differential
IAQ Sensor Value at 4mA
IAQ Sensor Value at 20mA
OAQ Sensor Value at 4mA
OAQ Sensor Vatue at 20mA
RH Sensor Value at 4mA
RH Sensor Value at 20mA
Alarm Relay Configuration
SPT/SPRH
Sensor Failure
SAT/RAT Sensor Failure
OAT Thermistor
Failure
Current Sensor Failure
Compressor
Failure
Refrigerant
Circuit Failure
SSP Transducer
Failure
SCT Thermistor
Failure
indoor Fan Failure
Dirty Filter
Thermostat
Failure
Economizer
Failure
Sensor Calibration
Space Temp Calibrafion
Space Temp Trim
Supply Air Temp Calib
Supply Air Temp Trim
Return Air Temp Calib.
Return Air Temp Trim
CCN Configuration
CCN Element
Number
CCN Bus Number
CCN Baud Rate
CCN Broadcast
Configuration
CCN Time/Date
Broadcast
CCN OAT Broadcast
Global Schedule
Broadcast
CCN Broadcast
Ack'er
CCN Schedule
Overrides
Schedule
Number
Accept
Global Holidays
Override Time Limit
Timed Override
Hours
SPT Override
Enabled
RANGE
UNITS
DEFAULT
CCN TABLE/SUB=TABLE
0=No IAQ
0: no FlOP
1 =Demand Venfilation
I : FlOP
2=Econ Position Override
3=Econ Min Position Control
0=Never
0
1=Only While Occupied
2=Always
0=No IAQ
0
I=DCV
Normally
Open
2=DCV Normally
Closed
3=Override
Normally
Open
4=Override
Normally
Closed
0=Never
0
1=Only While Occupied
2=Always
0 to 100
10
0to 100
30
0 to 100
100
0=No OAQ
0
1 =Demand Ventilation
2=Outdoor
Air Lockout
0 to 5000
600
0 to 5000
100
0 to 5000
700
0 to 5000
600
0 to 5000
200
0 to 5000
0
0 to 5000
2000
0 to 5000
0
0 to 5000
2000
0to50
%
0
60 to 100
%
I00
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
-30 to 120
dF
-30 to 30
^F
0
-30 to 130
dF
-30 to 30
^F
0
-30 to 130
dF
-30 to 30
^F
0
IAQ_CFG
ALM_CFG
CCNTRIM--see
Maintenance
Display)
CONFIGURATION
1 to 239
0 to 239
1=2400
2=4800
3:9600
4=19200
5:38400
Yes/No
No
Yes/No
No
Yes/No
No
Yes/No
No
0=Always
Occupied
0
1 to 64=Local
Schedule
65 to 99=Global
Schedule
Yes/No
No
0 to 4
hours
1
0 to 4
hours
0
Yes/No
Yes
not in CCN table)
not in CCN table)
not in CCN table)
BRODEFS
SCHEDOVR
CCN POINT
IAQANCFG
IAQANFAN
IAQiNCFG
IAQiNFAN
IAQMINP
ECONOMtN
IAQOVPOS
OAQANCFG
OAQLOCK
DAQ_LOW
DAQ HIGH
DAQFNON
DAQFNOFF
IAQ_4MA
IAQ 20MA
OAQ_4MA
OAQ 20MA
RH_4MA
RH_20MA
SPACE
AL
SATRATAL
OAT AL
CS _L
CO-MP AL
CKT
A_
SSPZAL
SCT AL
FANZAL
FILTAL
TSTAT_AL
ECON_AL
CCNBC
OATBC
GSBC
CCNBCACK
SCHEDNUM
HOLIDAYT
OTL
OVR EXT
TIME-OVER
PAGE NO.
39,49.82
41.51
39_49,50
49
49.50
49,50
39.49,50,
82
5O
49
49
5O
5O
49
49
5O
5O
47
47
52
64
64
64
64
64
35, 51
35, 51
35, 51
51
51
40,51
51
36, 40. 51
51
51
40.52
40, 52
FlOP -- Factory-Installed
Option
100