Carrier 50PG20-28 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 109

Single package rooftop units with comfortlink tmcontrols and puron (r-410a) refrigerant
Table of Contents

Advertisement

MODE -- CONFIGURATION
(cont)
ITEM
I
EXPANSION
CONFIGURATION
(cont)
OFC (cont)
3.OFF
Fan Lev3 Off Temperature
HMZR
REHT
R.DEC
R.INC
RH.FN
RF. LV
RF. ON
RF. OF
RA.LO
RA.LP
RA.HP
RB.LO
RB.LP
RB. HP
HEAT
HT.TY
N,HTR
MRT.H
MOT.H
H,DEC
H,INC
FOD,E
FOD.G
HT.LO
SAT.H
SPT
HT.PD
HT.ND
H,LAG
ECON
EC.EN
E.CTL
EC,MN
EC,MX
EH,LO
EL,LO
UEFC
Humidimizer Config
Humidimizer Equipped
Reheat2 Stage Decr.
Time
Reheat2 Stage Incr. Time
Reheat Fan Control
Reheat20DF
Fan On
Level
Reheat20DF
Fan On
Temp
Reheat20DF
Fan Off
Temp
Reheat2 OAT Limit A
Reheat2 SSP Lo Limit A
Reheat2 SSP Hi Limit A
Reheat2 OAT Limit B, C
Reheat2 SSP Lo
Limit B, C
Reheat2 SSP Hi
Limit B, C
Heating Configuration
Type of Heat Installed
Number of Heat Stages
Heat Minimum On Time
Heat Minimum Off Time
Heat Stage Decrease
Rate
Heat Stage Increase Rate
Fan-off Delay, Elect Heat
Fan-off Delay, Gas Heat
Heating Lockout Temp
SAT Heat Mode Sensing
Space Temperature
Sensor
SPT Heat Demand (+)
Level
SPT Heat Demand (-)
Level
Heat Thermal Lag Factor
Economizer Configuration
Economizer Installed
Economizer Control Type
Econo Minimum Position
Econo CooI Max Position
Econo Cool Hi Temp Limit
Econo Cool Lo Temp
Limit
Unoccupied Free Cooling
LEGEND
FlOP -- Factory-Installed
Option
RANGE
0 to 100 F
Yes/No
0 to 999 secs
0 to 999 secs
Yes/No
0to 3
0 to 100 F
0 to 100 F
20 to 70 F
50 to 100 psig
50 to 100 psig
20 to 70 F
50 to 100 psig
50 to 100 psig
0 = No Heat
1 = Gas
2 = Electric
1 to2
60 to 999 sec
60 to 999 sec
120 to 999 sec
120 to 999 sec
10 to 600 sec
45 to 600 sec
40 to 125 dF
Enable/Disable
0.5 to 5 ^F
-5 to -0.5 ^F
0 to 5 min
Yes/No
1=Digital, Position Feed-
back
2=Digital, Command
Feedback
3=Analog Control
0 to 100 %
0 to 100 %
40 to 100 dF
-30 to 50 dF
0=Disabled
1=Entire Unoccupied
Period
2=PreOccupancy
Time
DEFAULT
no Humidi-MiZer
FLOP:
55
Humidi-MiZer
FLOP:
78 (2O)
62 (24)
62 (28)
No: no Humidi-MiZer
FlOP
Yes: Humidi-MiZer
FlOP
6O
300
Yes
2
93 (20)
93 (24)
85 (28)
83 (20)
88 (24)
80 (28)
4O
8O
9O
5O
8O
9O
0 (50 series with no
electric heat)
(48 series)
2 (50 series with electric
heat)
(48 series 1-phase,
50 series <15kW)
2 (48 series 3-phase,
50 series >=15kW)
120
120
3OO
45O
30
45
75
Disable
No: no FlOP
Yes: FlOP
30
100
65
0
ENTRY
CL-3