Two methods are used to add and relnove stages of cooling
for units with more than one compressor. The first method
causes the unit to operate around its steady-state number of
stages. For example, if the correct number of stages is between
0 and 1, this method wilt cause the first stage to cycle. If the
correct number of stages is between 1 and 2, this method will
cause the second stage to cycle. The second method causes the
unit to find the steady-state nulnber of stages. Details of these
methods are provided below.
The control uses two methods to add a stage of compressor
cooling. The first method will add a stage of cooling when the
Cooling
Delnand
(Operating
Modes _'OOL---_gPT--+
DMD. 0
plus the change
in cool delnand
(Operating
Modes4DOL_9Pr-+rm).()
times the Cool Therlnal Lag
Factor (Operating Modes4DOL---_9PT4_.LA6)
is greater
than the SPY Cool Demand (+) Level (Operating Modes_
cOOL _gPr _(_z.PO).
DMD.C+ rRD.C*
C.LAG> (Z.PD
This method is only used after the Compressor Settling
Time ((bnfiguration--_U?_gT--_qAT.I),
has been exceeded
and the supply-air temperature is slowly increasing. The sec-
oM method will add a stage of cooling when Cool Demand is
greater than the SPT Cool Delnand (+) Level plus 0.5° F
(DMD.C > (Z.PD
+ 0.5) and the supply-air telnperature
(Operating Modes_,COOL--_AT--_AI)
is changing at a
rate greater than 0.3 ° F per minute.
The control uses two methods to relnove a stage of com-
pressor cooling. The first method will relnove a stage of cool-
ing when the Cooling Demand (Operating Modes4DOL
_gPT_OMO.
_) plus
the change in cool demand (Operating
Modes4DOL---_qPT_TRD._)
times the Cool Therlnal Lag
Factor (Operating Modes_OOL--_7PT_'.LAG)
is less
than the SPY Cool Demand @) Level (Operating Modes_
COOL---_gPT4Z.ND).
DMD.C+ fRO.C*
C.LAG< (Z.ND
This method is only used after the Compressor Settling
Time (SAT.!), has been exceeded and the supply air tempera-
ture is slowly decreasing. The second method will relnove a
stage of cooling when Cool Demand is less than the SPY Cool
Demand @) Level minus 0.5° F (DMD.C < (Z.ND
0.5) and
the supply air telnperature (SA!) is changing at a rate less than
0.2° F per minute.
Configurable
delays also apply when
adding
stages
((bnfiguration_COOL_.IN
0
or
relnoving
stages
((bnfiguration_COOL
_.DE
O.
Compressor
minimum
on-time (Configumtion_'COOL--_lIRT.
0
and minimum
off-time (Configuration _'OOL---_MOT..()
also apply.
OUTDOOR FANS
Each unit has a means for variable
outdoor airflow to control condenser pressure control within an
acceptable range by responding to varied operating modes and
alnbient temperatures. This is implemented dift_rently on
different units using multi-speed motors, multiple outdoor tans,
or variable-speed motor controllers.
NOTE: Factory default configurations account for these lnodel
ditthences and should not be changed. The default configura-
tions have been qualified over a lane range of conditions and
are provided in case a field replacement of a control board
occurs and the settings need to be checked or manually config-
ured. Outdoor fan operation is further described below to assist
in troubleshooting.
Units Without Humidi-MiZer
TM
System
The outdoor fan
speed, number, and location for each of three levels is defined
tbr each cooling circuit in the Circuit submenus (Configura-
tion_COOL_CIR.x).
Results of the factory configurations
are sho,a_ in Tables 38A-39B. The tan level selected during
operation is based on factory configurations
of outdoor
temperature limits and condenser pressure limits. These are in
the
Outdoor
Fan
Control
submenu
(Configuration--+
COOL _OF O. Initial thn level starts at zero and increments to
level 1when Fan LEV0 Max Pressure limit is reached. Chang-
es between levels 1 to 3 are initially selected based on outdoor
air temperature (OAT) input and the level On and Off tempera-
rare limits. The levels may be further adjusted based on the
circuit
saturated
condensing
temperatures
(Tempem-
tures--+REET--_7CT.x) and the level Max and Min pressure
limits.
Units With Humidi-MiZer System
Outdoor tan control for
Humidi-MiZer units includes a Motonnaster,_a)variable-speed
control for OFM 1 and OFM4. Contactor OFC 1 controls power
to the Motonnaster control. The Motorlnaster control automat-
icalty adjusts the outdoor thn speed to maintain approximately
80 to 100 F condenser telnperature for circuit A at all outdoor
ambient temperatures. Contactor OFC2 controls the relnaining
two Pans (48/50PG20) or relnaining 4 _ans (48/50PG24 and
28). The tan level operation is detennined
by some or all out-
door thn control configurations described above, plus addition-
at Humidilnizer confimlrations ((bnfiguration--->HZMR).
Table 38A -- Outdoor Fan Level Transitions
without Humidi-MiZer
System
FAN LEVEL
OUTDOOR
TEMPERATURE
(F)
Level 2 On
55 (size 20), 45 (sizes 24, 28)
Level 2 Off
50 (size 20), 40 (sizes 24, 28)
Level 3 On
65
Level 3 Off
55
Table 38B -- Outdoor
Fan Level Transitions
with Humidi-Mizer
System
FAN LEVEL
OUTDOOR TEMPERATURE
(F)
Level 2 On
88 (size 20), 8! (size 24 and 28)
Level 2 Off
57
Level 3 On
88 (size 20), 88 (size 24 and 28)
Level 3 Off
78 (size 20), 82 (size 24 and 28)
Table 39A -- Fan Level Control of Outdoor
Fan
Contactors
(1, 2, 3)without
Humidi-MiZer
System
FAN LEVEL
0
1
2
3
CIRCUIT
A
B
1 (20, 24)
3
1,3 (28)
1,2 (20)
2, 3(20)
2 (24, 28)
2 (24, 28)
1,2 (20, 24) 1, 2, 3 (28)
2, 3
Table 39B -- Fan Level Control of Outdoor
Fan
Contactors
(1 and 2) with Humidi-Mizer
System
FAN LEVEL
CIRCUITS A and B
0
1
1
1,2 (20)
2
2 (24-28)
3
1,2
Gas Heating
(48PG Units)--
For 48PG units, the
heat type confi_ration
Configuration -+HEAT---_HT.. T Y will
be thctory set to a value of 1.
Heat will not operate if the outdoor temperature
is
greater than the value configured for the heat lockout telnpera-
ture, (bnfiguration---yHEAT---yHT..LO. Minimum
on-time,
Configumtion---yHEAT---yMRT.H,
and lninilnum off-time,
Configulvttion---yHEAT---yMOT..H, tilnemmrds apply to both
stages of heating. Factory default values are 2 minutes On and
2 lninutes Off The IGC lninimum on-time of 1 lninute will be
followed even ifMRT.His lower and during Sel_:ice Test.