Carrier 50PG20-28 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 79

Single package rooftop units with comfortlink tmcontrols and puron (r-410a) refrigerant
Table of Contents

Advertisement

17
I
14
I
I
I
J1O
J11
RUN TEST
J12
(_
SEPARATION OF CIRCUITS TO EACH 24V TRANSFORMER MUST BE MAINTAINED
I......... I T55IFANSTATOSl
1
2
3
4
5
6
7
8
9
10
R
Y1 Y2 W1 W2
G
C
X
1
2
1
2
3
1
2
Fig. 25 -- Low-Voltage Terminal
Strip
LEN
CCN
Table 56 -- Field Connection
Terminal Strip
CONNECTION
TERMINAL
LABEL
DISPLAY NAME
POINT DESCRIPTION
SENSOR LOCATION
TYPE OF I/O
PIN NUMBER
1
24 VAC power
24 VAC output
J10, 17
2
IAQ
Indoor air quality sensor
return/space
4-20 mA input
J10, 16
3
Indoor & outdoor air quality common
4-20 mA input
J10, !5
4
OAQ or
Outdoor air quality sensor, or
economizer
SRRH
Space humidity sensor
space
4-20 mA input
J10, 14
5
RMOC
Remote occupancy
switch
field installed
24 VAC input
J10, !3
6
Outdoor enthalpy switch power
economizer
24 VAC input
J10, 11-12
ENTH or
Outdoor enthalpy switch, or
economizer, or
7
IAQ.S
Indoor air quality switch
return/space
24 VAC input
J1O, 9-10
8
EC.CP or EC.AP
Economizer actuator (digital control)
2-10 VDC output
J10, 6-8
EC.CP
Economizer actuator (analog control)
economizer
2-10 VDC output
9
Economizer signal common
economizer
VDC
J10, 3-5
10
EC.CP
Economizer actuator (digital control)
communication
EC.AP
Economizer actuator (analog control)
economizer
2-10 VDC output
J10, 1-2
R
24 VAC power
24 VAC output
Jl!,
11-14
Y1
Y1
Thermostat
Y1 (1st stage cool)
space
24 VAC input
J11 ,!0
Y2
Y2
Thermostat
Y2 (2nd stage coo!)
space
24 VAC input
J11, 9
W!
W1
Thermostat
W1 (1st stage heat)
space
24 VAC input
J11,7-8
W2
W2
Thermostat
W2 (2nd stage heat)
space
24 VAC input
J11,6
G
G
Thermostat
G (Fan)
space
24 VAC input
J11,5
C
24 VAC common
24 VAC output
J11,2-4
X
ALRM
Alarm output (normally open)
24 VAC output
J11, 1
FIRE SHUTDOWN
!-2,
FDWN
Fire shutdown switch
supply/return/space
switch input
J12, 6-7
or
HUM
Space humidity switch
space
HUMIDISTAT 1-2"
T55 1-2
SPT
Space temperature (T55t56)
space
10k thermistor
J12, 4-5
Space temperature offset (T56) or
space or return
10k thermistor
J12, 3-4
T55 2-3
SPTO or RAT
Return air temperature
LEN
Local Equipment Network (LEN)
communication
J13, 1-3, 4-5
CCN
Carrier Comfort Network (CCN)
communication
J13, 6-8, 4-5
TM
*Refer to Third Party Control section on page 38 for information on wiring fire shutdown with a Humidi-MiZer
system.
79