Input Channels - Fire-Lite 411UDAC Installation, Programming, Troubleshooting And Operating Instruction Manual

Fire alarm communicator
Table of Contents

Advertisement

Input Channels

2.4
Input Channels
The 411UDAC has four channel inputs. Channel/input field wiring is supervised for opens (trouble), shorts (alarm)
and ground faults (zero ohms impedance between panel and earth ground) by the 411UDAC. All conditions are visu-
ally and audibly annunciated and, if programmed, communicated to a Central Station.
Each channel is a Style B (Class B) Initiating Device Circuit with the exception of channel/input 3 which can be con-
figured for Style B or Style D (Class A). All inputs can be connected to normally-open contact type devices. In addi-
tion, inputs 1 and 3 can be connected to conventional 2-wire smoke detectors. Refer to Figure 2-6, "Wiring Initiating
Device Circuits," on page 24 for information on wiring Style B and Style D circuits.
The channel/inputs may be programmed as shown below:
• 2-wire smoke detector (inputs 1 & 3 only)
• Pull station
• Normally-open contact device
• Host panel trouble
• Supervisory
• Supervisory autoresettable
A maximum of five waterflow devices may be used on any circuit programmed as a waterflow zone per NFPA 72.
It is allowable to mix an assortment of device types (i.e. smoke detectors, heat detectors, pull stations, etc.) on any
zone. This is not recommended, however, since specific and detailed reports will not be possible (particularly critical
when using Contact ID format). For example, the report of general fire alarm versus pull station fire alarm or smoke
detector fire alarm could not be distinguished.
• Waterflow silenceable
• Waterflow nonsilenceable
411UDAC
Document #51073
Rev. D 12/09/2008
P/N 51073:D
23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Firewatch 411udac

Table of Contents