Components and Accessories

1.5
Components and Accessories
Main Circuit Board
The main circuit board contains the system's MCU (microcontroller unit), power supply, other primary
components and wiring interface connectors. The main circuit board is shipped in the same carton as the cabinet
but is not mounted in the cabinet. The circuit board should be installed only after the cabinet is mounted to the
wall and the area is clean and free of potential contaminants.
Cabinet
The cabinet is red and measures 14.5" (36.83 cm) high X 12.5" (31.75 cm) wide X 2.875" (7.303 cm) deep. It
provides space for up to two 7 Amp Hour batteries which must be ordered separately. A dress panel, which
mounts inside the cabinet, is also available. A supplied bezel must be installed in the door opening.
Dress Panel
An optional dress panel (P/N: DP-2) is available (required for Canadian installations). The dress panel restricts
access to the system wiring while allowing access to the membrane switch panel. See Figure 1-2 on page 9.
Transformer Assembly
One transformer is shipped in the same carton as the cabinet and main circuit board but not mounted in the
cabinet. The transformer should be installed before the cabinet is mounted to the wall.
Fire•Watch 411 Series DACT Programmer (Model PRO-411)
The PRO-411 is an optional DACT programmer which can be used to troubleshoot and program the 411UDAC,
as well as access the various modes of operation. The PRO-411 must be ordered separately.
PK-411UD Upload/Download Software Kit
The optional PK-411UD Kit consists of the PK-411UD Upload/Download software on 3½" disk and the
PK-411UD Program Manual. The PK-411UD enables a user to program the 411UDAC off site via the public
switched telephone network using any personal computer with Windows
1200 baud Hayes
1.6

Digital Communicator Operation

The 411UDAC has been designed to be compatible with a wide variety of fire alarm, nonfire and combination control
panels (Slave Mode operation). Numerous formats are also available for communication to a central station. Two
modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 and PH2 for the Pri-
mary and Secondary phone lines. The digital communicator provides the following functions:
• Line Seizure- takes control phone lines, disconnecting any premise phones which may be using the same lines
• Off/On-Hook - perform on and off-hook status to phone lines
• Listen for dial tone - 440 hertz tone typical in most networks
• Dialing the Central Station(s) phone number - default is Touch-Tone®, programmable to rotary
• Discern proper Central Station 'ACK' and 'Kiss-off' tone(s)
• Transmit data to the Central Station(s)
• Verify data has been accepted by the Central Station(s)
• Hang-up and release phone lines
• Communicate in a variety of formats (Refer to Table 4-1, "Format Selection Addresses ( 20 and 50) Program-
ming," on page 56).
14
®
compatible modem.
®
411UDAC
Document #51073
Rev. D 12/09/2008
®
3.1 or greater or Windows
P/N 51073:D
95 and a