Main Differences and Compatibilities with the FR-F500(L) Series

Item
Simple mode parameters 61
Pr. 0 Torque boost initial value
11K to 55K: 2%
User group 1 (16), user group 2 (16)
(Pr. 160, Pr. 173 to Pr. 175)
User initial value setting (Pr. 199)
Changed/cleared
functions
DC injection brake function with terminal (X13 signal)
(Pr. 11 setting value 8888, Pr. 180 to Pr. 186 setting
value 13)
Long wiring mode
(Pr. 240 setting 10, 11)
Intelligent optimum acceleration/deceleration
(Pr. 60 setting "3" and Pr. 61 to Pr. 63)
Automatic torque boost
(Pr. 38, Pr. 39)
Terminal block
Removable terminal block
PU
FR-PU04, DU04
Computer link, relay output option
Plug-in option
FR-A5NR
Three boards can be mounted
Installation size
FR-F500 (L)
Dedicated plug-in option (not compatible)
FR-F720-0.75K, 2.2K, 3.7K, 7.5K, 18.5K, 22K, 37K, 45K,
FR-F740-0.75K to 3.7K, 7.5K, 22K, 37K to 55K are compatible in mounting dimensions
For other capacities, an optional intercompatibility attachment (FR-AAT) is necessary.
FR-F700
Simple mode parameters 15
Pr. 0 Torque boost initial value
11K to 37K: 2%, 45K, 55K: 1.5%
(When the torque boost value of the FR-F500 series
used was the initial value, it is not necessary to change
the torque boost value from the initial value when
replacing with the FR-F700 series.)
User group (16) only
Setting methods were partially changed
(Pr. 160, Pr. 172 to Pr. 173)
"User initial value setting" (Pr. 199) was cleared
Substitutable with the copy function of the operation
panel (FR-DU07)
DC injection brake function with terminal was cleared
Start in reverse rotation is possible with flying start
function (frequency search of automatic restart after
instantaneous power failure function)
Setting is not necessary
(Pr. 240 settings "10" and "11" were cleared)
Function was cleared
For deceleration time, overvoltage alarm can be avoided
with regeneration avoidance function (Pr. 882 to Pr. 885).
Automatic torque boost was cleared because of addition
of "Simple magnetic flux vector" (Pr. 80)
Removable terminal block
Priority compatibility (Terminal block of the F500 can be
mounted)
FR-DU07
FR-DU04 unavailable (Partly restricted when the FR-
PU04 is used.)
Built into the inverter
(RS-485 terminals, relay output 2 points)
One board can be mounted
64