Change Of Du/Pu Monitor Descriptions Cumulative Monitor Clear; Change Of The Monitor Output From Terminal Fm And Am - Mitsubishi Electric FR-F700 Manual

F700 series
Hide thumbs Also See for FR-F700:
Table of Contents

Advertisement

Pr.
52, 54, 158, 170, 171, 268, 563, 564, 867, 891

Change of DU/PU monitor descriptions Cumulative monitor clear

Pr.52 DU/PU main display data selection Pr.54 FM terminal function selection
Pr.158 AM terminal function selection
Pr.171 Operation hour meter clear
Pr.563 Energization time carrying-over times
Pr.867 AM output filter
Pr.891 Cumulative power monitor digit shifted times
The monitor to be displayed on the main screen of the operation
panel (FR-DU07) / parameter unit (FR-PU04) can be selected.
Pr.52 Parameter
Types of Monitor
Increments
Output frequency
0.01Hz
0.01A/
Output current
0.1A
*6
Output voltage
0.1V
Alarm display
Frequency setting
0.01Hz
Running speed
1(r/min)
Converter output
0.1V
voltage
Regenerative brake
0.1%
duty
*5
Electronic thermal
relay function load
0.1%
factor
Output current peak
0.01A/
value
0.1A
*6
Converter output
0.1V
voltage peak value
0.01kW/
Input power
0.1kW
*6
0.01kW/
Output power
0.1kW
*6
Input terminal status
Output terminal
status
Option input
terminal status
Option output
terminal status
Load meter
0.1%
Reference voltage
output
Cumulative
1h
energization time
*2
Actual operation
1h
time
*2, 3
Motor load factor
0.1%
0.01kWh/
Cumulative power
0.1kWh
*4, *6
Variable
Power saving effect
according
to
Cumulative saving
parameters
power
PID set point
0.1%
PID measured value
0.1%
PID deviation value
0.1%
indicates simple mode parameters and
Pr.
Pr.170 Cumulative power meter clear
Pr.268 Monitor decimal digits selection
Pr.564 Operating time carrying-over times
Pr.54
Setting Value
(FM)
Full Scale
Pr.158
Value
DU
PU main
(AM)
LED
monitor
Setting
0/100
1
Pr.55
0/100
2
Pr.56
200V
class : 400V
0/100
3
400V
class : 800V
0/100
5
5
Pr.55
*1
Value of Pr. 55
represented in
6
6
*1
terms of Pr. 37
value
200V
class : 400V
8
8
*1
400V
class : 800V
Brake duty set
9
9
in Pr. 30 and
*1
Pr. 70
Electronic
thermal relay
10
10
*1
function
operation level
11
11
Pr.56
*1
200V
class : 400V
12
12
*1
400V
class : 800V
Rated inverter
13
13
*1
power × 2
Rated inverter
14
14
*1
power × 2
*1
55
*1
×
56
57
×
17
17
Pr.56
21
20
23
24
24
200%
25
Inverter
50
50
capacity
51
52
52
100%
53
53
100%
54
indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
*1
Selected by the parameter unit(FR-PU04)
*2
The cumulative energization time and actual operation time are
accumulated from 0 to 65535 hours, then cleared, and accumulated again
from 0.
When the operation panel (FR-DU07) is used, up to 65.53 (65530h) is
displayed as 1h=0.001 and then accumulated from 0.
*3
The actual operation time is not added up if the cumulative operation time
before power supply-off is less than 1h.
*4
When using the parameter unit (FR-PU04), "kW" is displayed.
*5
Setting can be made for the 75K or more.
*6
The setting depends on the inverter capacity.(55K or less/75K or more)⋅
⋅ The cumulative power monitor value digit can be shifted to the
right by the number set in Pr. 891.
⋅ By setting "0" in Pr. 170, the cumulative power monitor can be
cleared.
⋅ You can check the numbers of cumulative energization time
monitor exceeded 65535h with Pr. 563 and the numbers of actual
operation time monitor exceeded 65535h with Pr. 564.
⋅ Writing "0" in Pr. 171 clears the actual operation time monitor.
Pr. 268 Setting
9999 (initial value)
No function
When 1 or 2 decimal places (0.1 increments or 0.01
increments) are monitored, the decimal places are
0
dropped and the monitor displays an integer value (1
increments).
The monitor value of 0.99 or less is displayed as 0.
When 2 decimal places (0.01 increments) are
monitored, the 0.01 decimal place is dropped and the
monitor displays the first decimal place (0.1
1
increments).
When the monitor display digit is originally in 1
increments, it is displayed unchanged in 1
increments.
⋅ When Pr. 52 is set to "100", the set frequency monitor is displayed
during a stop and the output frequency monitor is displayed during
operation. (LED of Hz flickers during stop and is lit during
operation.)
0
During
operation/stop
Output
Output frequency
frequency
Output
current
Output
voltage
Alarm
display
⋅ Using Pr. 867 , the output voltage response of the terminal AM can
be adjusted within the range 0 to 5s.
Change of the monitor output
Pr.
55, 56
from terminal FM and AM
Pr.55 Frequency monitoring reference
Set the full-scale value to output the output frequency monitor
value to terminal FM and AM.
Set the full-scale value to output the output current monitor value
to terminal FM and AM in Pr. 56.
Pulse speed(terminal FM)
2400
pulse/s
1440
pulse/s
Output frequency
Pr.55
400Hz
reference
500A
Output current
Pr.56
reference
Description
Pr.52
100
During
During stop
running
Set frequency
Output frequency
Output current
Output voltage
Alarm display
Pr.56 Current monitoring reference
Output voltage(terminal AM)
10VDC
Pr.55
400Hz
500A
Pr.56
32