Resistor Unit; Connection Example - Mitsubishi Electric FR-F700 Manual

F700 series
Hide thumbs Also See for FR-F700:
Table of Contents

Advertisement

Name (type)
Brake unit
FR-BU-(H)
K

Resistor unit

FR-BR-(H)
K
53
The brake unit and resistor unit are options that will fully exhibit the regenerative braking capability of the inverter and are always used as a set.
There are six different brake units as in the following table, from which make selection according to the necessary braking torque and deceleration
time.
The brake unit is equipped with a seven-segment LED that displays the duty (%ED) and alarm.
Brake unit selection table
%ED at short-time rating when braking torque is 100%
Motor Capacity
5.5kW 7.5kW 11kW 15kW 18.5kW 22kW 30kW 37kW 45kW 55kW
200V
5.5K
Inverter
400V
5.5K
2
FR-BU-15K
80
0
- --- --
FR-BU-30K
%ED
0
- --- --
V
FR-BU-55K
4
80
FR-BU-H15K
0
- --- --
FR-BU-H30K
%ED
0
V
- --- --
FR-BU-H55K
Braking torque (%) at short-time rating when 10%ED is 15s
Motor Capacity
5.5kW 7.5kW 11kW 15kW 18.5kW 22kW 30kW 37kW 45kW 55kW
200V
5.5K
Inverter
400V
5.5K
2
280
FR-BU-15K
Braking
0
FR-BU-30K
Torque
- --- --
0
(%)
- --- --
V
FR-BU-55K
4
280
FR-BU-H15K
Braking
0
- --- --
FR-BU-H30K
Torque
0
(%)
- --- --
V
FR-BU-H55K
Brake unit and resistor unit combinations and used cables
Brake Unit Type
Resistor Unit Type
2
FR-BU-15K
FR-BR-15K
0
FR-BU-30K
FR-BR-30K
0
FR-BU-55K
FR-BR-55K
V
4
FR-BU-H15K
FR-BR-H15K
0
FR-BU-H30K
FR-BR-H30K
0
FR-BU-H55K
FR-BR-H55K
V
Use the wires of the above recommended size or larger.

Connection example

MCCB
Three-phase AC
power supply
*1. Connect the inverter terminals (P/+, N/-) and brake unit (FR-BU (H)) terminals so that their
terminal signals match with each other.
(Incorrect connection will damage the inverter.)
*2. When the power supply is 400V class, install a step-down transformer.
Specifications, Structure, etc.
7.5K
11K
15K
18.5K
22K
30K
7.5K
11K
15K
18.5K
22K
30K
40
15
10
--- ---
- --- --
- --- --
- --- --
65
30
25
15
10
- --- --
- --- --
- --- --
90
60
30
40
15
10
--- ---
- --- --
- --- --
- --- --
65
30
25
15
10
- --- --
- --- --
- --- --
90
60
30
7.5K
11K
15K
18.5K
22K
30K
7.5K
11K
15K
18.5K
22K
30K
200
120
100
80
70
- --- --
- --- --
260
180
160
130
100
- --- --
- --- --
- --- --
300
250
180
200
120
100
80
70
- --- --
- --- --
260
180
160
130
100
- --- --
- --- --
- --- --
300
250
180
Cable (P/+-P/+, N/--
(Note) 1. The temperature rise of the resistor unit is about a
N/-, P/+-P, PR-PR)
2
3.5mm
2
5.5mm
2
14mm
2
3.5mm
2
3.5mm
2
5.5mm
ON
T
*2
MC
MC
FR-BR
Motor
R/L1
U
P
TH1
S/L2
V
IM
PR
T/L3
W
TH2
Inverter
FR-BU
PR
P/+
*1
N/−
N/−
*3
5m or less
37K
45KK
55K
37K
45KK
55K
- --- --
- --- --
- --- --
- --- --
- --- --
- --- --
20
15
10
- --- --
- --- --
- --- --
- --- --
- --- --
- --- --
20
15
10
37K
45KK
55K
37K
45KK
55K
- --- --
- --- --
- --- --
80
70
------
Resistor unit
150
120
100
- --- --
- --- --
- --- --
80
70
- --- --
150
120
100
maximum of 100°C. Therefore, use heat-resistant wires
(such as glass wires).
*3
Inverter
FR-BU
OFF
P/+
P/+ P/+
N/-
N/-
PR
Within
Within
5m
5m
Inverter
FR-BU
Twist
P/+
P/+ P/+
N/-
N/-
PR
HA
Within 10m
HB
HC
*3. Minimize the cable length between the inverter and brake
unit and the resistor unit and brake unit. Use a twisted
cable when the wiring length exceeds 5m. (If twisted
wires are used, the distance should be within 10m.) Use
the wires of the above recommended size or larger.
Brake unit
FR-BR
P
PR
FR-BR
Twist
P
PR
Within 10m