Selection Of Regeneration Unit; Avoid Mechanical Resonance Points (Frequency Jump); Speed Display And Speed Setting; Detection Of Output Frequency - Mitsubishi Electric FR-F700 Manual

F700 series
Hide thumbs Also See for FR-F700:
Table of Contents

Advertisement

Selection of
Pr.
30, 70
regeneration unit
Pr.30 Regenerative function selection
Use the high power factor converter (FR-HC) to reduce
harmonics, improve the power factor, or continuously use the
regenerative mode.
For the 75K or more, use the brake unit MT-BU5 or BR5 when the
regenerative brake duty is need to be increased due to frequent
starts and stops. Use the high power factor converter MT-HC to
reduce harmonics, improve the power factor, or continuously use
the regenerative mode.
<55K or less>
Pr.30 Setting
0 (initial value)
Brake unit (FR-BU, BU)
High power factor converter (FR-HC),
2
power regeneration common converter (FR-CV)
<75K or more>
Pr.30 Setting Pr.70 Setting *
0 (initial value)
0%
1
10%
2
* Pr.70 Special regenerative brake duty can be set for the 75K or more inverter.
Avoid mechanical resonance
Pr.
31 to 36
points (frequency jump)
Pr.31 Frequency jump 1A
Pr.33 Frequency jump 2A
Pr.35 Frequency jump 3A
When it is desired to
avoid resonance
attributable to the
natural frequency of a
mechanical system,
these parameters allow
resonant frequencies to
be jumped.
Up to three areas may be set, with the jump frequencies set to
either the top or bottom point of each area.
The value set to 1A, 2A or 3A is a jump point and operation in the
jump zone is performed at these frequencies.
Frequency jump is not performed if the initial value is set to "9999".
During acceleration/deceleration, the running frequency within the
set area is valid.
Speed display and speed
Pr.
37, 144
setting
Pr.37 Speed display
You can change the PU (FR-DU07) monitor display or frequency
setting to motor speed or machine speed.
When the running speed monitor is selected, each monitor and
setting are determined according to the combination of Pr. 37 and
Pr. 144. (The units within the thick frame are the initial values.)
Output
Pr. 37
Pr. 144
Frequency
Setting
Setting
Monitor
0
Hz
2 to 10
Hz
0
102 to
r/min
*1
110
0
Hz
1 to
Machine
2 to 10
9998
speed
*1
102 to
Hz
110
31
indicates simple mode parameters and
Pr.
Pr.70 Special regenerative brake duty *
Regeneration Unit
Regeneration Unit
Not used
Power regeneration converter (MT-RC)
Brake unit (MT-BU5)
High power factor converter (MT-HC)
Pr.32 Frequency jump 1B
Pr.34 Frequency jump 2B
Pr.36 Frequency jump 3B
Frequency jump
Pr.36
Pr.35
Pr.34
Pr.33
Pr.32
Pr.31
Pr.144 Speed setting switchover
Frequency
Set
Running
Setting
Frequency
Speed
Parameter
Monitor
Monitor
Setting
Hz
r/min
Hz
*1
Hz
r/min
Hz
*1
r/min
r/min
r/min
*1
*1
Machine
Hz
Hz
speed
*1
Machine
Machine
Machine
speed
speed
speed
*1
*1
Hz
r/min
Hz
*1
indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
*1
Motor speed r/min conversion formula
....... Frequency × 120/number of motor poles (Pr. 144)
Machine speed conversion formula
...... Pr. 37 × frequency/60Hz
For Pr. 144 in the above formula, the value is "Pr. 144-100" when "102 to
110" is set in Pr. 144 and the value is "4" when Pr. 37=0 and Pr.144=0.
*2
The increments for Hz are 0.01Hz, machine speed are 1m/min and r/min
are 1r/min
.
Pr.
41 to 43, 50
Pr.41 Up-to-frequency sensitivity
Pr.43 Output frequency detection for reverse rotation
Pr.50 Second output frequency detection
The inverter output frequency is detected and output at the
output signals.
If the set frequency is considered as 100%, output frequency can
be adjusted between ±1% and ±100% with Pr. 41.
This parameter can be used to ensure that the running frequency
has been reached to provide the operation start signal etc. for
related equipment.
SU
When the output frequency reaches or exceeds the setting of Pr.
42, the output frequency detection signal (FU) is output.
This function can be used for electromagnetic brake operation,
open signal, etc.
When the detection frequency is set in Pr. 43, frequency detection
for reverse rotation use only can also be set. This function is
effective for switching the timing of electromagnetic brake
operation between forward rotation (rise) and reverse rotation
(fall) during vertical lift operation, etc.
When outputting a frequency detection signal besides the FU
signal, set the detection frequency to Pr. 50 . The FU2 signal is
output when the output frequency reaches or exceeds the Pr. 50
setting.
Output
frequency
OFF
FU
OFF
FU2
Pr.
Refer to the section about Pr.7, Pr.8
44, 45
Pr.
Refer to the section about Pr. 0.
46
Pr.
Refer to the section about Pr. 3.
47
Refer to the section about Pr. 22 and other
Pr.
48, 49
relevant parameters.
Refer to the section about Pr. 41 and other
Pr.
50
relevant parameters.
Pr.
Refer to the section about Pr. 9.
51
*1
*1
Detection of output frequency (SU,
FU, FU2 signal)
Pr.42 Output frequency detection
Running frequency
Adjustment
range Pr.41
Time
OFF
OFF
ON
Pr.50
Forward
rotation
Pr.42
Reverse
rotation
OFF
OFF
ON
ON
ON
OFF
ON
OFF
Time
Pr.43
Pr.50