Mitsubishi Electric FR-F700 Manual page 17

F700 series
Hide thumbs Also See for FR-F700:
Table of Contents

Advertisement

Type
Terminal Symbol
Relay output 1 (alarm
A1, B1, C1
output)
A2, B2, C2
Relay output 2
RUN
Inverter running
SU
Up to frequency
OL
Overload alarm
Instantaneous power
IPF
failure
FU
Frequency detection
Open collector output
SE
common
FM
For meter
AM
Analog signal output
PU connector
PU connector
TXD+
Inverter transmission
TXD-
terminal
RS-485
RXD+
Inverter reception
terminal
RXD-
terminal
SG
Earth (Ground)
CAUTION
The inverter will be damaged if power is applied to the inverter output terminals (U, V, W). Never perform such wiring.
indicates that terminal functions can be selected fromPr. 178 to Pr. 196 (I/O terminal function selection)
*1. Low indicates that the open collector output transistor is on (conducts). High indicates that the transistor is off (does not conduct).
*2. Not output during inverter reset.
Terminal Name
Changeover contact output indicates that the inverter protective function has activated and the
output stopped. Abnormal: No conduction across B-C (Across A-C Continuity), Normal: Across
B-C Continuity (No conduction across A-C) Contact capacity: 230VAC 0.3A (Power factor=0.4)
30VDC 0.3A
1 changeover contact output Contact capacity: 230VAC 0.3A (Power factor=0.4) 30VDC 0.3A
Switched low when the inverter output frequency is equal to or
higher than the starting frequency (initial value 0.5Hz). Switched
high during stop or DC injection brake operation.
Switched low when the output frequency reaches within the range
of ±10% (initial value) of the set frequency. Switched high during
acceleration/deceleration and at a stop.
Switched low when stall prevention is activated by the stall
prevention function. Switched high when stall prevention is
cancelled.
*1
Switched low when an instantaneous power failure and under
voltage protections are activated.
Switched low when the inverter output frequency is equal to or
higher than the preset detected frequency and high when less than
the preset detected frequency.
Common terminal for terminals RUN, SU, OL, IPF, FU
Select one e.g. output frequency from monitor items. *2
The output signal is proportional to the magnitude of the
corresponding monitoring item.
With the PU connector, communication can be made through RS-485.
(for connection on a 1:1 basis only)
. Conforming standard
. Transmission format
. Communication speed : 4800 to 38400bps
. Overall length
With the RS-485 terminal, communication can be made through RS-485.
Conforming standard
Transmission format
Communication speed
Overall length
Description
*1
*1
*1
*1
: EIA-485(RS-485)
: Multidrop
: 500m
: EIA-485 (RS-485)
: Multidrop link
: 300 to 38400bps
: 500m
Permissible load 24VDC
0.1A
(a voltage drop is 3.4V
maximum when the signal
is on)
Alarm code (4bit) output
(Refer to page 36)
Output item:
Output frequency (initial
setting)
Permissible load current
2mA
1440 pulses/s at 60Hz
Output item:
Output frequency (initial
setting)
Output signal 0 to 10VDC
Permissible load current
1mA (load impedance
10kΩ or more) Resolution
8 bit
18