Fig. 8 - Ferroli F24 Installation, Servicing And User Instructions Manual

Gas combination boiler for central heating and hot water production, wall mounted, copper heat exchanger, fan assisted, room sealed, electronic flame ignition and control installation, service and user instructions
Table of Contents

Advertisement

2.06 Pump characteristics
The pump head available for circulating the water is given in fig.
7.
N.B. - The pump is factory set at position 3. The pump is a
Grundfos type 15-50 UPS series.
Grundfos Pump per formance graph
Note - Minimum flow through boiler heat exchanger at any
time should not fall below 6 litres per minute.
If the total volume of water in the system exceeds 40 litres
an additional expansion vessel must be fitted to the central
heating return pipe.
1 2 3 Speed settings
Boilers pressure drop
A
Available pump head C.H.
B
SIZING OF ADDITIONAL EXPANSION VESSELS:
Deduct from the value given in the table the 8 litre
vessel supplied.
Note:
1. Fill C.H. installation to min. 1.5 bar.
2. Expansion vessel must be fitted to central heating
return pipe.
3. The standard 7 litre expansion vessel is charged
to 1 bar.
4. The additional expansion vessel should be charged
to 1 bar.
Pressure loss diagram
H
8
8
mbar x 100
7
6
5
4
3
2
1
0
0.5
Fig. 7
SAFETY VALVE
SETTING (bar)
VESSEL CHARGE
PRESSURE (bar)
INITIAL SYSTEM
PRESSURE (bar)
TOTAL WATER
CONTENT of SYSTEM
LITRES
25
50
75
100
125
150
175
200
For syst. volumes other than
those given above, mult. the syst.
volume by the factor across
1
1.5
2
2.5
Ferroli F24
3.0
0.5
1.0
1.5
2.0
1.5
EXPANSION VESSEL VOLUME (litres)
3.5
6.5
13.7
4.7
7.0
12.9
27.5
9.5
10.5
19.4
41.3
14.2
14.0
25.9
55.1
19.0
17.5
32.4
68.9
23.7
21.0
38.8
82.6
28.5
24.5
45.3
96.4
33.2
28.0
51.8
110.2
38.0
0.140
0.259
0.551
0.190

Fig. 8