7.12 Spark or fl ame detect electrode (fig. 38)
• Isolate gas and electricity supply
• Remove outer case (two screws bottom rear
corners)
• Open room sealed compartment and

combustion chamber

• Identify electrode from fig. 38
• Unplug electrical connection "A" from sensing
electrode
• Remove fixing screw and remove flame detect
electrode
• Remove the two fixing screw from spark
electrode plate and remove it.
7.13 D.H.W. fl owmeter
• Isolate electricity and water supplies
• Open a hot water tap to release water pressure
from the domestic side of the heat exchanger,
close tap.
• Remove outer case (two screws bottom rear
corners).
• Remove two screws from control panel and tilt
forward
• Take off protective cover from main PCB and
unplug flow meter lead from terminal X4.
• Place a piece of cloth or some other absorbent
material over rear of control panel to catch
any drops of water that may be released when
removing the flow meter
• Using a 24mm open ended spanner, undo flow
meter unions "A" and "B" taking care not to
twist the copper tubing (access through base
panel).
• Remove flow meter, check + clean filter +
restrictor + fit to new flow meter.
• Reassemble in reverse order.
Take care on correct position of
components as reported in fi g. 39b