Ferroli F24 Installation, Servicing And User Instructions Manual page 18

Gas combination boiler for central heating and hot water production, wall mounted, copper heat exchanger, fan assisted, room sealed, electronic flame ignition and control installation, service and user instructions
Table of Contents

Advertisement

For further accessories please refer to:
"Flue system manual for room sealed
boiler"Example of calculation for wall
inlet/outlet with 2 pipe system
maximum total fl ue length: 48 metres
3.04.4 Example of other installation with two pipe systems
Example of wall inlet/outlet
2 pipe application
18
Attention:
Ref.
1
2
3
4
5
6
7
Fig. 20
Example of direct roof fl ue outlet
and wall air inlet
Fig. 21
Resistance of flue restrictor (if req.)
is included (see table on page 13)
Remove the flue restrictor.
The flue and air pipes must have an inclination
downward equal to 3% from boiler to outside.
N° of
Description
pieces
1
Air bend 80 mm R/D = 0,75
13
Horizontal air pipe
1
Air wall terminal
1
Air inlet closing flange
1
Flue bend 80 mm R/D = 0,75
12
Horizontal flue
1
Air wall terminal outlet flue
Fig. 22
Ferroli F24
Length or
Code
reduction
1,5 m
13,0 m
2,0 m
2,5 m
24,0 m
5,0 m
Total 48,0 m
Example of roof
inlet/outlet
Fig. 23