Pr.
Explanation
Transmission Speed
09.08
for USB Card
Communication
09.09
Protocol for USB
Card
Transmission Fault
09.10
Treatment for USB
Card
Time-out Detection
09.11
for USB Card
COM port for PLC
Communication
09.12
(NOT for VFD*E*C
models)
CANopen
Communication
09.13
Address (ONLY for
VFD*E*C models)
CANbus Baud Rate
09.14
(ONLY for VFD*E*C
models)
Gain of CANbus
Frequency
09.15
(ONLY for VFD*E*C
models)
CANbus Warning
09.16
(ONLY for VFD*E*C
models)
0: Baud rate 4800 bps
1: Baud rate 9600 bps
2: Baud rate 19200 bps
3: Baud rate 38400 bps
4: Baud rate 57600 bps
0: 7,N,2 for ASCII
1: 7,E,1 for ASCII
2: 7,O,1 for ASCII
3: 8,N,2 for RTU
4: 8,E,1 for RTU
5: 8,O,1 for RTU
6: 8,N,1 (Modbus, RTU)
7: 8,E,2 (Modbus, RTU)
8: 8,O,2 (Modbus, RTU)
9: 7,N,1 (Modbus, ASCII)
10: 7,E,2 (Modbus, ASCII)
11: 7,O,2 (Modbus, ASCII)
0: Warn and keep operating
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and keep operating
0.1 ~ 120.0 seconds
0.0: Disable
0: RS485
1: USB card
0: disable
1: 1 to 127
0: 1M
1: 500K
2: 250K
3: 125K
4: 100K
5: 50K
0.00~2.00
bit 0 : CANopen Guarding Time out
bit 1 : CANopen Heartbeat Time out
bit 2 : CANopen SYNC Time out
bit 3 : CANopen SDO Time out
bit 4 : CANopen SDO buffer overflow
bit 5 : CAN Bus Off
bit 6 : Error protocol of CANopen
bit 7 : CANopen boot up fault
Group 10 PID Control Parameters
English- 26
Settings
Factory
NOTE
Setting
2
1
0
0.0
0
1
5
1.00
Read-
only