Pr.
Explanation
Mid-Point
01.40
Frequency (Fmid)
(Motor 3)
Mid-Point Voltage
01.41
(Vmid) (Motor 3)
Minimum Output
01.42
Frequency (Fmin)
(Motor 3)
Minimum Output
01.43
Voltage (Vmin)
(Motor 3)
Source of First
02.00
Master Frequency
Command
Source of First
02.01
Operation
Command
02.02
Stop Method
PWM Carrier
02.03
Frequency
Selections
Motor Direction
02.04
Control
0.10 to 600.0 Hz
115V/230V series: 0.1V to 255.0V
460V series: 0.1V to 510.0V
0.10 to 600.0 Hz
115V/230V series: 0.1V to 255.0V
460V series: 0.1V to 510.0V
Group 2 Operation Method Parameters
0: Digital keypad UP/DOWN keys or Multi-
function Inputs UP/DOWN. Last used
frequency saved.
1: 0 to +10V from AVI
2: 4 to 20mA from ACI or 0 to +10V from
AVI2
3: RS-485 (RJ-45)/USB communication
4: Digital keypad potentiometer
5: CANopen communication
For VFD*E*C models, the factory setting is 5
0: Digital keypad
1: External terminals. Keypad STOP/RESET
enabled.
2: External terminals. Keypad STOP/RESET
disabled.
3: RS-485 (RJ-45)/USB communication.
Keypad STOP/RESET enabled.
4: RS-485 (RJ-45)/USB communication.
Keypad STOP/RESET disabled.
5: CANopen communication. Keypad
STOP/RESET disabled.
For VFD*E*C models, the factory setting is 5
0: STOP: ramp to stop; E.F.: coast to stop
1: STOP: coast to stop; E.F.: coast to stop
2: STOP: ramp to stop; E.F.: ramp to stop
3: STOP: coast to stop; E.F.: ramp to stop
1 to 15kHz
0: Enable forward/reverse operation
1: Disable reverse operation
2: Disabled forward operation
English- 14
Settings
Factory
NOTE
Setting
1.50
10.0
20.0
1.50
10.0
20.0
1
1
0
8
0