Download Print this page

Delta AC Motor Drives VFD-XXXE Getting Started Manual page 22

Delta electronics ac motor drives quick start manual

Advertisement

Pr.
Explanation
06.11
Fourth Most Recent
Fault Record
Fifth Most Recent
06.12
Fault Record
07.00
Motor Rated Current
(Motor 0)
Motor No-Load
07.01
Current (Motor 0)
Torque
07.02
Compensation
(Motor 0)
Slip Compensation
07.03
(Used without PG)
(Motor 0)
Motor Parameters
07.04
Auto Tuning
Motor Line-to-line
07.05
Resistance R1
(Motor 0)
Motor Rated Slip
07.06
(Motor 0)
Slip Compensation
07.07
Limit
Torque
07.08
Compensation Time
Constant
Slip Compensation
07.09
Time Constant
Accumulative Motor
07.10
Operation Time
(Min.)
Accumulative Motor
07.11
Operation Time
(Day)
Motor PTC
07.12
Overheat Protection
Input Debouncing
07.13
Time of the PTC
Protection
Motor PTC
07.14
Overheat Protection
Level
Settings
27: DCBUS error (cF3.3)
28: IGBT Overheat (cF3.4)
29: Power Board Overheat (cF3.5)
30: Control Board CPU WRITE failure
(cF1.1)
31: Control Board CPU WRITE failure
(cF2.1)
32: ACI signal error (AErr)
33: Reserved
34: Motor PTC overheat protection (PtC1)
35-39: Reserved
40: Communication time-out error of control
board and power board (CP10)
Group 7 Motor Parameters
30 %FLA to 120% FLA
0%FLA to 99% FLA
0.0 to 10.0
0.00 to 10.00
0: Disable
1: Auto tuning R1
2: Auto tuning R1 + no-load test
0~65535 mΩ
0.00 to 20.00 Hz
0 to 250%
0.01 ~10.00 Sec
0.05 ~10.00 sec
0 to 1439 Min.
0 to 65535 Day
0: Disable
1: Enable
0~9999(*2ms)
0.1~10.0V
English- 22
Factory
NOTE
Setting
FLA
0.4*FLA
0.0
0.00
0
0
3.00
200
0.30
0.20
0
0
0
100
2.4

Advertisement

loading