Download Print this page

Delta AC Motor Drives VFD-XXXE Getting Started Manual page 24

Delta electronics ac motor drives quick start manual

Advertisement

Pr.
Explanation
Motor Line-to-line
07.36
Resistance R1
(Motor 3)
Motor Rated Slip
07.37
(Motor 3)
Motor Pole Number
07.38
(Motor 3)
DC Brake Current
08.00
Level
DC Brake Time
08.01
during Start-Up
DC Brake Time
08.02
during Stopping
Start-Point for DC
08.03
Brake
Momentary Power
08.04
Loss Operation
Selection
Maximum Allowable
08.05
Power Loss Time
Base-block Speed
08.06
Search
B.B. Time for Speed
08.07
Search
Current Limit for
08.08
Speed Search
Skip Frequency 1
08.09
Upper Limit
Skip Frequency 1
08.10
Lower Limit
Skip Frequency 2
08.11
Upper Limit
Skip Frequency 2
08.12
Lower Limit
Skip Frequency 3
08.13
Upper Limit
Skip Frequency 3
08.14
Lower Limit
08.15
Auto Restart After
Fault
Auto Reset Time at
08.16
Restart after Fault
Settings
0~65535 mΩ
0.00 to 20.00 Hz
2 to 10
Group 8 Special Parameters
0 to 100%
0.0 to 60.0 sec
0.0 to 60.0 sec
0.00 to 600.0Hz
0: Operation stops after momentary power
loss
1: Operation continues after momentary
power loss, speed search starts with the
Master Frequency reference value
2: Operation continues after momentary
power loss, speed search starts with the
minimum frequency
0.1 to 5.0 sec
0: Disable speed search
1: Speed search starts with last frequency
command
2: Starts with minimum output frequency
0.1 to 5.0 sec
30 to 200%
0.00 to 600.0 Hz
0.00 to 600.0 Hz
0.00 to 600.0 Hz
0.00 to 600.0 Hz
0.00 to 600.0 Hz
0.00 to 600.0 Hz
0 to 10 (0=disable)
0.1 to 6000 sec
English- 24
Factory
NOTE
Setting
0
3.00
4
0
0.0
0.0
0.00
0
2.0
1
0.5
150
0.00
0.00
0.00
0.00
0.00
0.00
0
60.0

Advertisement