Pr.
Explanation
02.05
Line Start Lockout
Loss of ACI Signal
02.06
(4-20mA)
02.07
Up/Down Mode
Accel/Decel Rate of
Change of
02.08
UP/DOWN
Operation with
Constant Speed
Source of Second
02.09
Frequency
Command
Combination of the
First and Second
02.10
Master Frequency
Command
Keypad Frequency
02.11
Command
Communication
02.12
Frequency
Command
The Selections for
Saving Keypad or
02.13
Communication
Frequency
Command
Settings
0: Disable. Operation status is not changed
even if operation command source Pr.02.01
is changed.
1: Enable. Operation status is not changed
even if operation command source Pr.02.01
is changed.
2: Disable. Operation status will change if
operation command source Pr.02.01 is
changed.
3: Enable. Operation status will change if
operation command source Pr.02.01 is
changed.
0: Decelerate to 0 Hz
1: Coast to stop and display "AErr"
2: Continue operation by last frequency
command
0: by UP/DOWN Key
1: Based on accel/decel time
2: Constant speed (Pr.02.08)
3: Pulse input unit (Pr.02.08)
0.01~10.00 Hz
0: Digital keypad UP/DOWN keys or Multi-
function Inputs UP/DOWN. Last used
frequency saved.
1: 0 to +10V from AVI
2: 4 to 20mA from ACI or 0 to +10V from
AVI2
3: RS-485 (RJ-45)/USB communication
4: Digital keypad potentiometer
5: CANopen communication
For VFD*E*C models, the factory setting is 5
0: First Master Frequency Command
1: First Master Frequency Command+
Second Master Frequency Command
2: First Master Frequency Command -
Second Master Frequency Command
0.00 to 600.0Hz
0.00 to 600.0Hz
0: Save Keypad & Communication
Frequency
1: Save Keypad Frequency only
2: Save Communication Frequency only
English- 15
Factory
NOTE
Setting
1
1
0
0.01
0
0
60.00
60.00
0