Delta AC Motor Drives VFD-XXXE Getting Started Manual page 19

Delta electronics ac motor drives quick start manual

Advertisement

Pr.
Explanation
Digital Terminal
04.10
Input Debouncing
Time
04.11
Min AVI Voltage
04.12
Min AVI Frequency
04.13
Max AVI Voltage
04.14
Max AVI Frequency
04.15
Min ACI Current
04.16
Min ACI Frequency
04.17
Max ACI Current
04.18
Max ACI Frequency
04.19
ACI/AVI2 Selection
04.20
Min AVI2 Voltage
Min AVI2 Frequency 0.0 to 100.0%
04.21
04.22
Max AVI2 Voltage
Max AVI2
04.23
Frequency
The Digital Input
Used by PLC
04.24
(NOT for VFD*E*C
models)
The Analog Input
Used by PLC
04.25
(NOT for VFD*E*C
models)
Display the Status of
04.26
Multi-function Input
Terminal
Settings
Bit11:MI12
0:N.O., 1:N.C.
P.S.:MI1 to MI3 will be invalid when it is 3-
wire control.
1 to 20 (*2ms)
0.0 to 10.0V
0.0 to 100.0%
0.0 to 10.0V
0.0 to 100.0%
0.0 to 20.0mA
0.0 to 100.0%
0.0 to 20.0mA
0.0 to 100.0%
0: ACI
1: AVI2
0.0 to 10.0V
0.0 to 10.0V
0.0 to 100.0%
Read only.
Bit0=1:MI1 used by PLC
Bit1=1:MI2 used by PLC
Bit2=1:MI3 used by PLC
Bit3=1:MI4 used by PLC
Bit4=1:MI5 used by PLC
Bit5=1:MI6 used by PLC
Bit6=1: MI7 used by PLC
Bit7=1: MI8 used by PLC
Bit8=1: MI9 used by PLC
Bit9=1: MI10 used by PLC
Bit10=1: MI11 used by PLC
Bit11=1: MI12 used by PLC
Read only.
Bit0=1:AVI used by PLC
Bit1=1:ACI/AVI2 used by PLC
Bit2=1: AI1 used by PLC
Bit3=1: AI2 used by PLC
Read only.
Bit0: MI1 Status
Bit1: MI2 Status
Bit2: MI3 Status
Bit3: MI4 Status
Bit4: MI5 Status
Bit5: MI6 Status
Bit6: MI7 Status
Bit7: MI8 Status
English- 19
Factory
NOTE
Setting
1
0.0
0.0
10.0
100.0
4.0
0.0
20.0
100.0
0
0.0
0.0
10.0
100.0
##
##
##