2-7 Restrictions
2-7-1 The behavior of 2 word number in the NS-Designer test function
In the temperature controller, a value equivalent to 2 words (32 bits) is stored for each
communications address, but in the test function, the first 16 bits and the last 16 bits behave
as one and the same value. For that reason, test function will not operate successfully when
2 word numbers are designated.
2-7-2 Address display when address error occurs
When faulty device is set to communications address set in functional object, this
communications address is displayed in the device setting error dialogue.
If the communications address is allocated to the temperature controller, not the address for
the temperature controller set with the NS-Designer, but the address in the PLC address
format is displayed. Addresses will be converted as shown below.
Address displayed when faulty device is set to communications address
<Device>
3
2
1
0
15 14 13
0
Unit No.
0 to 31
<Device>
DM
0
EM
2
EM0_
4
EM1_
6
EM2_
8
EM3_
10
EM4_
12
EM5_
14
EM6_
16
EM7_
18
EM8_
20
EM9_
22
EMA_
24
EMB_
26
EMC_
28
WR
30
24
0000 to 7FFF
Word address
12
11 10
9
8
Ch
<variable>
0-3
0 to F
CH address of temperature controller
Unit
No.
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
7
6
5
4
3
2
<address>
0000 to 007F
<Variable >
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
00 to 15
Bit position
1
0
7
6
5
4
0
0
0
0
Bit position
0 to 31
Temp
controller
<Address>
Variable
C0
C1
0000 to 003F
C2
C3
0040 to 007F
C4
C5
C6
C7
0000 to 007F
C8
C9
CA
CB
CC
CD
0040 to 007F
CE
CF
0000 to 003F
D0
D1
0040 to 007F
D2
D3
0000 to 003F
D4
D5
0040 to 007F
D6
D7
0000 to 003F
3
2
1
0

Advertisement

Table of Contents
loading

Table of Contents