Specifications

■ Ratings
Supply voltage
Operating voltage range
Power consumption
Sensor input
Control
Relay output
output
Voltage output (for driving the SSR) 12 VDC, 21 mA (with short-circuit protection circuit)
Control method
Alarm output
Setting method
Indication method
Other functions
Ambient temperature
Ambient humidity
Storage temperature
■ Characteristics
Setting accuracy
Indication accuracy
(ambient temperature of 23° C)
Influence of temperature
Influence of voltage
Hysteresis (for ON/OFF control)
Proportional band (P)
Integral time (I)
Derivative time (D)
Alarm output range
Control period
Sampling period
Insulation resistance
Dielectric strength
Vibration
Malfunction 10 to 55 Hz, 20 m/s
resistance
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hr each in X, Y, and Z directions
Shock resistance
Malfunction 100 m/s
Destruction 300 m/s
Life expectancy
Electrical
Weight
Degree of protection
Memory protection
EMC
Approved standards
Conformed standards
Note: 1. The following exceptions apply to thermocouples.
• U, L: ±2° C ±1 digit max.
• R:
±3° C ±1 digit max. at 200° C or less
2. The following exceptions apply to platinum resistance
thermometers.
Input set values 0, 1, 2, 3 for E5CSV: 0.5% FS ±1 digit max.
Input set value 1 for E5CSV: 0.5% FS ±1 digit max.
Temperature Controllers E5CSV
2
Temperature Controllers
100 to 240 VAC, 50/60 Hz
85% to 110% of rated supply voltage
5 VA
Multi-input (thermocouple/platinum resistance thermometer) type: K, J, L, T, U, N, R, Pt100, JPt100
SPST-NO, 250 VAC, 3A (resistive load)
ON/OFF or 2-PID (with auto-tuning)
SPST-NO, 250 VAC, 1A (resistive load)
Digital setting using front panel keys (functionality set-up with DIP switch)
3.5 digit, 7-segment digital display (character height: 13.5 mm) and deviation indicators
• Setting change prohibit (key protection)
• Input shift
• Temperature unit change (° C/° F)
• Direct/reverse operation
• Control period switching
• 8-mode alarm output
• Sensor error detection
-10 to 55° C (with no condensation or icing)
25% to 85%
-25 to 65° C (with no condensation or icing)
Thermocouple (See note 1.):
Platinum resistance thermometer (See note 2.): (±0.5% of indication value or ±1° C, whichever is greater) ±1 digit max.
R thermocouple inputs:
Other thermocouple inputs:
Platinum resistance thermometer inputs: (±1% of PV or ±2° C, whichever is greater) ±1 digit max.
0.1% FS
1 to 999° C (automatic adjustment using auto-tuning/self-tuning)
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning)
Absolute-value alarm: Same as the control range
Other:
0% to 100% FS
0.2° C or ° F (fixed)
Alarm hysteresis:
2/20 s
500 ms
20 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity
2
for 10 min each in X, Y, and Z directions
2
min., 3 times each in 6 directions
2
min., 3 times each in 6 directions
100,000 operations min. (relay output models)
Approx. 120 g (Controller only)
Front panel: Equivalent to IP66; Rear case: IP20; Terminals: IP00
EEPROM (non-volatile memory) (number of writes: 1,000,000)
EMI Radiated:
EMI Conducted:
ESD Immunity:
Radiated Electromagnetic Field Immunity:
Conducted Disturbance Immunity:
Noise Immunity (First Transient Burst Noise): EN 61000-4-4
Burst Immunity:
Surge Immunity:
Voltage Dip/Interrupting Immunity:
UL 61010C-1 (listing), CSA C22.2 No.1010-1
EN 61326, EN 61010-1, IEC 61010-1, VDE 0106 Part 100 (finger protection), when the terminal cover is mounted.
E5CSV
24 VAC/VDC, 50/60 Hz
3 VA/2 W
(±0.5% of indication value or ±1° C, whichever is greater) ±1 digit max.
(±1% of PV or ±10° C, whichever is greater) ±1 digit max.
(±1% of PV or ±4° C, whichever is greater) ±1 digit max.
EN 55011 Group 1 Class A
EN 55011 Group 1 Class A
EN 61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
EN 61000-4-3: 10 V/m (80-1000 MHz, 1.4-2.0 GHz amplitude modulated) (level 3)
10 V/m (900 MHz pulse modulated)
EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 2)
2 kV power-line (level 3), 1 kV I/O signal-line (level 3)
EN 61000-4-5: Power line:
Output line (relay output): Normal mode 1 kV; Common mode 2 kV
EN 61000-4-11 0.5 cycle, 100% (rated voltage)
Normal mode 1 kV; Common mode 2 kV
5