Specifications - Omron E5CN-FR Manual

Limit controller
Table of Contents

Advertisement

Specifications

■ Ratings
Item
Power supply
voltage
Operating voltage range
Power consumption
Sensor input
Control output FM Limit output
relay
Alarm output
Event input
Contact input
Non-contact input ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
External power supply for ES1B
Setting method
Indication method
Other functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
■ Input Ranges
Thermocouples/Platinum Resistance Thermometers
Platinum resistance
Input Type
thermometer
Name
Pt100
3200
3000
2300
1500
1500
1400
1300
1200
1100
1000
900.0
900
800
700
600
500
400
300
210.0
200
100
0
0.0
−100.0
−200.0
−199.9
−300.0
−300
Setting number
0
1
2
The applicable standards for the input types
are as follows:
K, J, T, E, N, R, S, B: IEC584-1
L: Fe-CuNi, DIN 43710-1985
85% to 110% of rated supply voltage
7.5 VA max.
Models with temperature inputs
Thermocouple: K, J, T, E, L, U, N, R, S, or B
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor: 10 to 70 ° C, 60 to 120 ° C, 115 to 165 ° C, or 160 to 260 ° C
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations,
minimum applicable load: 5 V, 10 mA
SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations,
minimum applicable load: 1 V, 1 mA
ON: 1 k Ω max., OFF: 100 k Ω min.
Outflow current: Approx. 7 mA per point
12 VDC ±10%, 20 mA, Short-circuit protection provided.
Digital setting using front panel keys
11-segment digital display and individual indicators
Character height: PV: 11 mm, SV: 6.5 mm
• Limit over continuation time measurement function
• Limit over max./min. value measurement function
• Annunciator output
• Input error output
• PV display two-color switching function
• Input digital filter
• Input compensation
• Protection functions
− 10 to 55 ° C (with no icing or condensation), for 3-year warranty: − 10 to 50 ° C
25% to 85%
− 25 to 65 ° C (with no icing or condensation)
JPt100
K
J
2300
1500
900.0
900.0
750.0
210.0
0.0
0.0
0.0
−100
−199.9
−300
3
4
5
6
7
8
U: Cu-CuNi, DIN 43710-1985
Pt100: IEC 751
100 to 240 VAC, 50/60 Hz
Thermocouple
T
E
L
U
1500
1100
700
700
700
700
0
−100
−199.9
−199.9
−300
−300
9
10
11
12
13
14
Limit Controller
Infrared temperature
10 to
60 to
N
R
S
B
70ºC
120ºC
3200
3000
3000
2300
300
190
0
0
0
−300
15
16
17
18
19
Shaded settings are the default settings.
E5CN-FR
sensor
115 to
160 to
165ºC
260ºC
500
320
240
0
0
0
20
21
22
3

Advertisement

Table of Contents
loading