Initial Setup

Typical Example
This example shows how to perform initial setup for the E5AR-Q4B
(100 to 240 VAC) and is based on the following conditions.
Input type: Pt100 ( 200.0 to 850.0 C)
Control method: PID control
Output: Pulse voltage output
Control period: 0.5 s
Alarm 1: Upper limit alarm at 5.0 C
Alarm 2: Absolute-value upper limit alarm at 200.0 C
PID: Obtained by auto-tuning (AT)
SP: 150.0 C
1. Power ON
Power ON
Operation level
25 . 0
Control stops.
Input initial setting level
i1-t
The input
type is
displayed.
Input initial setting level
Change the
i1-t
2. Set input type
input type
with the
UD Keys.
Control initial setting level
Change the
o1-t
output type
with the
UD Keys.
3. Set control mode
mode
Check the
control mode.
Alarm setting level
alt1
Check the
alarm type.
4. Set alarm type
Change the
alt2
alarm type
with the
UD Keys.
PV/SP/MV
0
0
.
0
0
.
Press for 3 s min. l.0 will appear in the
No. 3 display (input initial setting level).
Setting area 1
l.0
Input 1 type
2 : K (1) 200.0 to 1300.0 C
2
l.0
UD
l.0
Input 1 type
2 0 :
0
l.0
Pt100 (1) 200.0 to 850.0 C
Press for less than 1 s. l.1 will appear
in the No. 3 display (control initial setting level).
l.1
M indicates
Output 1 type
0
1 0 : Pulse voltage output
that the M Key
l.1
is pressed
repeatedly until
M
the desired
Control mode
setting is
0
0 : Standard PID control
displayed.
l.1
Press for less than 1 s. l.3 will
appear in the No. 3 display (alarm setting level).
l.3
Alarm 1 type
2
2 : Upper limit alarm
l.3
M
Alarm 2 type
2 8 : Absolute-value
8
l.3
upper limit alarm
Press for 1 s min. to return to the operation level.
SSR
COM
SUB1
SUB2
IN1
OUT1
Voltage output:
12 VDC
Control stops.
Operation level
25.0
0.0
0.0
Adjustment level
bank
l.adj
M
Change the
cp
5. Change the control period
control period
0.5
with the
l.adj
UD Keys.
Bank setting level
Check that
[ 1
bnk
.
the displayed
l.bnk
bank selection
is 0.
M
Set alarm
0.al-1
6. Set alarm value 1
value 1 with
5.0
the UD
l.bnk
Keys.
M
Set alarm
0.al-2
7. Set alarm value 2
value 2 with
200.0
the UD
l.bnk
Keys.
PID setting level
d.pid
l.pid
Operation level
25
Set the SP
150.0
8. Set the SP
with the
0.0
UD Keys.
Adjustment level
bank
l.adj
M
9. Execute AT
Execute AT
at
with the
l.adj
UD Keys.
Operation level
25.0
150.0
0.0
10. Start operation
Start operation
Digital Controllers
Temperature sensor:
Control
Pt100
object
Alarm 1
Alarm 2
PV/SP/MV
Less than 1 s
l.adj
Bank number
0
0 : Bank 0
M indicates
that the M Key
is pressed
Control period (heating)
repeatedly until
20.0 0.5 : 0.5 s
the desired
setting is
displayed.
Less than 1 s
l.bnk
Displayed bank selection
0
0 : Bank 0
Bank 0 alarm value 1
0.0 5.0 : 5.0 C
M indicates
that the M Key
is pressed
Bank 0 alarm value 2
repeatedly until
0.0 200.0 : 200.0 C
the desired
setting is
displayed.
Less than 1 s
l.pid
Displayed PID selection
1
1 : PID No.1
Less than 1 s
PV/SP/MV
0.0 150.0 : 150.0 C
Less than 1 s
l.adj
Bank number
0
0 : Bank 0
During AT
Bank number
0
off 0 : AT execution
l.adj
Less than 1 s
After AT
PV/SP/bank number
E5AR/E5ER
at
0
at
off
l.adj