Creating I/O Tables; I/O Tables - Omron CJ2 CPU - REV 10-2010 User Manual

Cj2 cpu unit software
Table of Contents

Advertisement

4-3

Creating I/O Tables

You must create I/O tables only in the following cases. I/O tables are created by using the CX-Program-
mer.
• To check for incorrect connections
• To reserve words
It is not necessary to create I/O tables if checking for incorrect connection is not required and automatic
allocation is acceptable.

4-3-1 I/O Tables

The type and location of Units connected to the CPU Unit are registered in the I/O tables. If I/O tables
are created, the system will check if the types and locations of the Units actually connected to the CPU
agree with the data registered in the I/O tables when the CPU Unit is tuned ON.
The I/O tables can be made based on the actually connected Units when the CX-Programmer is online,
or they can be manually set when the CX-Programmer is offline and then transferred to the CPU Unit.

I/O Tables

CJ2H-CPU68-EIP
00
0000
CJ1W-ID201
01
2000
CJ1W-AD041-V1
02
1500
CJ1W-CLK21-V1
03
0001
Open slot
04
0001
Open slot
Location
I/O memory
(slot number)
area address
CX-Programmer
The CPU Unit automatically verifies with the connected Units (actual I/O tables) mounted to it according
to this data.
• If there is a mismatch, an I/O setting error will occur, and operation will not start.
CJ2 CPU Unit Software User's Manual
CPU Unit
Unit type
I/O tables can be made using the
CX-Programmer online for the actual
Units or edited offline as desired and
then transferred to the CPU Unit.
4 CPU Unit Initialization
Units
00 01 02
CJ1W-CLK21-V1
CPU Bus Unit
CJ1W-AD041-V1
Special I/O Unit
CJ1W-ID201
Basic I/O Unit
4
4-9

Advertisement

Table of Contents
loading

Table of Contents