9-3-6

Serial Port Settings

The following parameters are valid when pin 5 on the DIP switch on the CPU Unit is OFF (default).
Communications Settings
Parameter
Communica-
• Standard (9600: 1, 7, 2, E):
tions Settings
Standard settings
• Custom: Any setting

• Serial Port Settings

Set the serial port settings in the PLC Setup when you need to change these settings from the
defaults. Specify the frame format when no-protocol mode is selected.
The port settings can also be changed with STUP(237). The Serial Port Settings Changing Flag
(A619.02) is turned ON when STUP(237) is executed and it is turned OFF when the port settings
have been changed.
When pin 5 of the DIP switch on the front of the CPU Unit is ON, the CPU Unit automatically detects
the communications parameters of a Programming Device (including a Programming Console) con-
nected to the RS-232C port. Those automatically detected parameters are not stored in the PLC
Setup.
CJ2 CPU Unit Software User's Manual
Settings
Default
Standard
Function
The standard settings (9600: 1, 7, 2, E)
are for Host Link Mode, 1 start bit, 7
data bits, even parity, 2 stop bits, and a
baud rate of 9,600 bps.
Set custom settings to use any other
communications settings.
9 PLC Setup
Related flags and
words
A619.02
(Serial Port Settings
Changing Flag)
9
9-23