SEND
Instruction
NETWORK SEND
Symbol
Applicable Program Areas
Function block
Area
definitions
Usage
OK
Operands
Operand
S
First source word (local node)
D
First destination word (remote node)
C
First control word
C: First Control Word
15
C
15
12
11
C+1
#0: Fixed
15
C+2
Destination node address: (See note 4.)
00 to maximum node address (hex)
(Depends on the network.
Example: In the case of Controller Link,
CS/CJ/NSJ Series Instructions Reference Manual (W474)
Mnemonic
Variations
SEND
@SEND
SEND(090)
Block program areas
Step program areas
OK
OK
Description
0
Number of send words
0001 to maximum data length (hex)
(Depends on the network.
Example: In the case of Controller Link,
&1 to 990 decimal or
#0001 to 03DE hex (1 to 990 words))
8
7
4
3
0
Destination network address:
#00 to 7F hex (0 to 127)
#00: Local network (See note 2.)
Serial port number (physical port) (See note 1.)
#0: Not used
#1: Port 1
#2: Port 2
#3: Reserved
#4: Reserved
8
7
0
Destination unit address:
#00 to FE hex (See note 5.)
#00 to 20 hex (0 to 32)
#FF: Broadcast))
Function
code
090
Sends data to a node in the network.
SEND
S: First source word (local node)
S
D: First destination word (remote node)
D
C
C: First control word
Subroutines
OK
Data type
UINT
UINT
WORD
3. Instructions
Function
SFC action or
Interrupt tasks
transition programs
OK
OK
Size
Variable
Variable
5
3
879