Omron CJ - INSTRUCTIONS REFERENCE MANUAL 07-2009 Reference Manual page 887

Programmable controllers
Hide thumbs Also See for CJ - INSTRUCTIONS REFERENCE MANUAL 07-2009:
Table of Contents

Advertisement

3. Instructions
Related Auxiliary Area Words and Bits
Name
Peripheral Port Parameters Changing Flag
RS-232C Port Parameters Changing Flag
Port Parameters Changing Flags for ports 1 to 4 on
Serial Communications Units 1 to 15.
Port Parameters Changing Flags for ports 1 to 4 on
the Serial Communications Board (CS Series only)
Note The Settings Changing Flags for port 3 and port 4 are reserved for future use.
Function
STUP(237) writes 10 words of data from S to S+9 to the communications setup area of the Unit with the
specified unit address, as shown in the following table. When the constant #0000 is designated to S, the
communications settings of the corresponding port will be set to default.
Unit address
00 hex
CPU Unit
Unit No. + 10 hex
Serial Communications Unit (CPU
Bus Unit)
E1 hex
Serial Communications Board (Inner
Board) (CS Series only)
The following data is stored in the 10 words from S to S+9.
Peripheral port on CPU Unit
RS-232C port built into CPU Unit
Serial Communications Unit port 1
Serial Communications Unit port 2
Serial Communications Board port 1
Serial Communications Board port 2
When STUP(237) is executed, the corresponding Port Parameters Changing Flag (A619.01, A619.02,
or A619 to A636) will turn ON. The flag will remain ON until changing the parameters has been
completed.
Note If the PLC is turned OFF and then ON again after STUP(237) has been used to change the communications
parameters, the new parameters will be retained or will revert to the previous parameters, depending on the
CPU Unit.
CPU Unit
CJ2, CS1-H, CJ1-H,
CJ1M, or CS1D
CS1/CJ1
850
Address
A619.01
A619.02
A620 bit 01 to bit 04
to A635 bit 01 to bit 04
A636.01 to A636.04
Unit
Port No.
1 hex
2 hex
1 hex
2 hex
1 hex
2 hex
PLC Setup settings in Programming Console addresses
+144 to +153
PLC Setup settings in Programming Console addresses
+160 to +169
m to m+9 (m = D30000
m+10 to m+19 (m = D30000 ¥ unit number)
D32000 to D32009
D32010 to D32019
Status of communications parameters
If the PLC is turned OFF and then ON again, the communications parameters revert
to the settings that existed before they were changed with STUP(237).
If the PLC is turned OFF and then ON again, the communications parameters set
with STUP(237) are retained.
Contents
ON when the communications parameters are being changed for the
peripheral port.
ON when the communications parameters are being changed for the RS-
232C port.
ON when the communications parameters are being changed for a port
on a Serial Communications Unit.
ON when the communications parameters are being changed for a port
on the Serial Communications Board.
Serial port
Serial port communications setup area
Peripheral Port
Communications parameters for the peripheral
port in the PLC Setup (Cannot be specified for a
CJ2 CPU Unit.)
RS-232C Port
Communications parameters for the RS-232C port
in the PLC Setup
Port 1
10 words starting from D30000 + 100
Port 2
10 words starting from D30000 + 100
10
Port 1
10 words starting from D32000
Port 2
10 words starting from D32010
unit number)
CS/CJ/NSJ Series Instructions Reference Manual (W474)